Product Details:
Payment & Shipping Terms:
|
Description:
This solution is designed for remote area without AC mains power. It uses solar + generator power supply, and uses batteries as energy storage component.
Item |
Technical Parameter |
Load |
1100W, DC 48V ( provided by the customer) |
Equipment Compartment Cooling |
1500W, AC220V air conditioner |
Battery Compartment Cooling |
500W, AC220V air conditioner |
Generator Power Supply |
80hours |
Battery backup power supply |
18hours |
Ingress Protection |
Equipment compartment, battery compartment: IP55 Generator compartment: IP45 |
Note:
1.The batteries charge and discharge frequency is high, so we recommend to use Iron Lithium Battery. The advantages of Iron Lithium Batteries are: anti - high temperature (up to 55°C), high battery cycle times, deep discharge, large current charge.
2.About the air conditioner, we recommend to use AC air conditioner, which is with high cost performance ratio.
Working Principle:
1. In case of the solar cell panel working normally:
(1) During the daytime, the solar power provide power supply for load and battery charge; In the nighttime, the batteries discharge and supply power for the load.
(2) We assume the standard sunshine intensity is 6 hours in the area, the batteries working time is 24 - 6 = 18 hours.
2. In case of cloudy and rainy days, without sunlight:
(1) The batteries discharge; when the batteries voltage is lower than 44V, the UPS will send switch signals and start the generator, then the generator will start to provide power supply for batteries and load.
(2) When the batteries voltage is restored to 53.5V, the generator will be turned off.
System Principle Diagram:
Layout Pictures
Component List
NO. |
Item |
Quantity |
Specs |
1 |
Solar Cell Panel, Bracket |
1 |
11200W |
2 |
UPS 1 |
1 |
3KW |
3 |
Iron Lithium Battery |
1 |
48V700Ah |
4 |
Solar Controller |
1 |
48V250A |
5 |
Generator |
1 |
Single Phase, 20KW |
6 |
AC&DC PDU |
1 |
Grade B Lightening Protection, 5-way DC input, 2- way AC output |
7 |
Cabinet 1 (Equipment Compartment + Battery Compartment) |
1 |
|
8 |
Cabinet 2 (Generator Compartment) |
1 |
|
9 |
AC air conditioner 1 |
1 |
Cooling: 1.5KW, Power Consumption: 550W, AC230V |
10 |
AC air conditioner 2 |
1 |
Cooling: 500W, Power Consumption: 250W, AC230V |