Home ProductsDC48V Air Conditioner

TC06-40ZEH/01,400W,DC48V Air Conditioner,For Outdoor Telecom Cabinet/UPS Room/Base Station

Certification
Good quality Two Compartments Outdoor Telecom Cabinet for sales
Good quality Two Compartments Outdoor Telecom Cabinet for sales
Timely response, professional skills, rigorous attitude, fast delivery, we are very satisfied, cooperation is very smooth.

—— Manish

From 1 sample to 45 sets, 76 sets, 200sets, we gradually established a strong trust. The cabinet quality is good and the design is reasonable.

—— Parmar

In the past three years, our cooperation is very cheerful, thanks for your company's technical support and patient service, the end user is very satisfied with the quality of outdoor telecom cabinet with cooling. Best wishes to our future cooperation.

—— Anthony

The air conditioner have been running for one and a half years. Cooling effective is good. Good after-sale service, and patiently instruct to use and solve technical problems. Environmental monitoring system is also running well, and remote monitoring the cabinet is very convenient.

—— Luis Alberto

I'm Online Chat Now

TC06-40ZEH/01,400W,DC48V Air Conditioner,For Outdoor Telecom Cabinet/UPS Room/Base Station

China TC06-40ZEH/01,400W,DC48V Air Conditioner,For Outdoor Telecom Cabinet/UPS Room/Base Station supplier

Large Image :  TC06-40ZEH/01,400W,DC48V Air Conditioner,For Outdoor Telecom Cabinet/UPS Room/Base Station

Product Details:

Place of Origin: China
Brand Name: ESTEL
Certification: ISO9001:2008
Model Number: TC06-40ZEH/01

Payment & Shipping Terms:

Minimum Order Quantity: 1 Set
Packaging Details: Wooden Case
Delivery Time: 15~20 Days
Payment Terms: T/T,L/C
Supply Ability: 10000 Sets
Contact Now
Detailed Product Description

400W DC48V AIR CONDITIONER

Model: TC06-40ZEH/01

1. Introduction

The TC06-40ZEH/01 air conditioner is a full automation temperature control product. It uses intelligent controller to control the whole system of the air conditioner. According to the variation of environment temperature, the intelligent controller can automatically detect, operate and record the whole system’s operating time, power consumption, event and historical data. It can store 100 event records and 1280 historical data records, and can enquire 256 days’ daily record information. The product is widely applied in telecom cabinet, small and medium sized telecom room, UPS room, outdoor base station room, etc.
 
2. Features
 
(1)Strong adaptability
(2)High intelligence 
(3)High precision
(4)High reliability
(5)Low noise 
(6)Low energy consumption
(7)With 4 way switching value detection
(8)With 1 way room air conditioner control
(9)Wide input voltage range: 48VDC±15%  
(10)With dry contact alarm output 
 
3. System Principle Diagram

TC06-40ZEH/01,400W,DC48V Air Conditioner,For Outdoor Telecom Cabinet/UPS Room/Base Station

Diagram 1: System Principle Diagram

 

4. Standard Compliance

Standard 

Description

GB/T 17626.7-1998 

Electromagnetic compatibility 

GB4706.1

Safety of household appliance and electrical appliance with similar use.

GB4798.1

Environmental conditions existing in the application for electric and electronic products - storage

GB4798.2

Environmental conditions existing in the application for electric and electronic products - transportation

GB4798.3

Environmental conditions existing in the application for electric and electronic products - usage

 

5. Technical Parameters

 

Model No.

TC06-40ZEH/01

Environmental Performance 

working environmental temperature

-20°C ~ 55°C

storage working temperature

-40°C ~ 70°C

working humidity

≤95%

Thermal Performance

rated cooling capacity

550W(L35 L35)

450W(L25 L35)

heating input power 

no

 

Electrical Performance

rated input current 

3.5A(L35 L35)

3.3A(L25 L35)

rated input power 

168W(L35 L35)

158W(L25 L35)

input voltage

DC48V

Reliability

MTBF

60000 hours

Noise

≤65dB

 

TC06-40ZEH/01,400W,DC48V Air Conditioner,For Outdoor Telecom Cabinet/UPS Room/Base Station

   Diagram 2:  Dimension Diagram

6. Installation and Electrical Wiring 
 
6.1 Preparation Before Installation
 
(1) Prepare the tools in the following table “Installation And Maintenance Tools”.
(2)Check the air vents to ensure there’s no unnecessary items on the vents.
 
6.2 Installation And Maintenance Tools
 

Tools Name

Function

Cross Screwdriver

Fix air conditioner.

Small Slotted Screwdriver

Wire power supply port on the panel

Wire Stripper 

Wire stripping 

Wire Crimper

Crimp power supply for equipment

Multimeter

Check the wiring to ensure it’s correctly connected and without short circuit.

Clamp Meter

Test operating current of the air conditioner

 
6.3 Installation Steps
 
(1)Make sure the air conditioner is not connected with power.
(2)Fix the air conditioner according to the Dimension Diagram.
(3)Strip the insulation of the power supply wire, and crimp the terminal.
(4)Connect the wires according to the Electrical Wring Diagram.
(5)After finishing the wiring, use the multimeter to check if the electric circuit is normal. Then connect the air conditioner with power supply, and use clamp meter to test the operating current. 
Note: Make sure to disconnect all the power supply to the air conditioner before installation. Choose proper wire diameter and test operating current according to the technical parameters of the air conditioner.             
 
6.4 Electrical Wiring Diagram
 
TC06-40ZEH/01,400W,DC48V Air Conditioner,For Outdoor Telecom Cabinet/UPS Room/Base Station
 
Diagram 3: Wiring Diagram
 
Wiring Ports:
 
0V -48V: power supply input (voltage input: 48VDC±15%)
F+  F- : direct ventilation output 
AL1 AL2: general alarm output
A+ B- SGND: RS485 communication interface
N: not connected pin
 
7. After mechanical installation and electrical installation are finished, check the installation items.
 
(1)Make sure the air conditioner is firmly installed.
(2)Check the electrical installation circuit, and ensure it doesn’t have short circuit.
(3)Check the air outlet, air inlet, internal fan and external fan of the air conditioner, and ensure they don’t have any odds and ends.
(4) Connect the air conditioner to power supply, and test the power supply (voltage input: 48VDC±15%), operating current 3.4A±4%.
 
8. System Control 
 
Terminology:
 
BTH: Temperature & Humidity of Box;
ETH: Temperature & Humidity of Engine Room;
BAC: Box Air Conditioning;
CAC: Cabinets Air Conditioning;
BACS: Box Air Conditioning Start Times;
BACR: Box Air Conditioning Run Time;
CACS: Cabinets Air Conditioning Start Times;
CACR: Cabinets Air Condintioning Run Time;
VP Temp.: Vent-pipe Temperature;
AC FSV: Air Conditioning Value of Current;
CPar: Parameter of Control;
BPar: Parameter of Base;
A/M: Automatic / Manual;
MaxTemp: Maximum Temperature;
MixTemp: Minimum Temperature.
 
8.1 Application
 
ET872 thermostatic battery cabinet controller is a type of universal intelligent controller. It is controlled by highly integrated STC single chip microcomputer. It can intelligently control operating and hydrogen exhaust of thermostatic cabinet air conditioner, and can control a telecom room air conditioner. It have the following functions: fault self diagnosis, power on self start, restart after unexpected failures caused by other reasons.
  
The controller features perfect performance, easy and fast installation and setting, which is widely used in telecom cabinet, small and medium sized telecom room, UPS room, outdoor base station room, etc.
 
8.2 Main Technical Parameters
 
a.2×16 Chinese/English shift LCD display, user friendly; 
b.Simultaneously display temperature and humidity inside the box and communication room temperature;    
c.Temperature measurement accuracy: 0.1 °C; humidity measurement accuracy:4%;
d.Can store 180 days’ daily event record, 1 record every day;
    Daily highest temperature, lowest temperature, average temperature
    Daily event record;
e.Save the former day’s daily data at 0:00 every day; Can query 180 days’ daily record information;
f.RS485 or RS232 communication,RTU-Modbus protocol, support remote detection and control;
g.Use PID control algorithm, intelligently adjust output power, optimize energy efficiency;  
h.Controllable air conditioner quantity: 2 sets. 1 set of air conditioner for communication room, and 1 set of air conditioner for thermostatic cabinet.
i.Control mode: pulse (Non dry contact air conditioner), conducting (dry contact air conditioner);
j.Real-time control air conditioner on/off
k.Power supply: DC48V;
l.Power consumption:≤5W;
m.Working environment: -30°C~70°C; <90%RH;
n.Installation method: guide rail,hanging;
o.Dimension(L*W*H):150mm×190mm×45mm
 
8.3 Operating Instruction
 
ET872 uses user-friendly interfaces, which can be operated easily. All the operations can be realized with four buttons. The following is the control board diagram:
 
TC06-40ZEH/01,400W,DC48V Air Conditioner,For Outdoor Telecom Cabinet/UPS Room/Base Station
 
Diagram 4  Control Board Diagram
 
8.3.1 Buttons
 
PgDn:page down button, confirm button.      
Press once and release the button, page down;
A long press on the button, enter or exit parameter status;
At operating status: can select five display interfaces;
At parameter status: revise, confirm and parameter page down button; a long  press on the button to exit parameter status.
 
▲:increasing parameter revision. Page down button for event query.  
 
▼:decreasing parameter revision. Page up button for event query.
 
PgUp: page up button; the function is oppose to PgDn operation.
 
8.3.2 Indicators
 
When the air conditioner works normally, the Work indicator flashes at 2s frequency, showing it is working normally. When there is screen saver, the indicator can indicate the system is working normally.
 
When the system has alarm, the Alarm indicator will turn on, showing alarm occurs. 
 
8.3.3 Operating Interfaces 
 
The controller includes three working modes: operating mode, parameter mode, and query mode.
 
(1) Operating Mode:
 
The mode is normal working mode. There are five operating interfaces which can be selected. The five interfaces display different content. When they are not selected, the interfaces will automatically shift. Press the button “PgDn” to select next display interface; press the button “PgUp” to select the previous display interface.   
 
Interface 1: 
 
Line 1: temperature and humidity inside the thermostatic box (or area I);
Line 2: temperature and humidity inside communication room (or area II);
Diagram 4 is the first interface (main interface) of this mode.
 
Interface 2: 
 
Line 1: control status indication. Separated by the sign “/”, the former is box air conditioner status: “OFF” means compressor and heater both stop; “30%-100%” means compressor output percentage; “¤” means heater are working; “♂” means hydrogen exhaust or direct ventilation. The latter is cabinet air conditioner status: “Off” means stop; the first “*” means cabinet air conditioner control; the second “*” or “>” is actual status, means the air conditioner is at cooling status; If it display “>”, it means the air conditioner only blow air. 
 
Line 2: real time, manual/auto status. “Auto” means auto status, “Menu” means manual status.
 
At manual mode of this interface, press buttons “▲,▼” can manually increase or reduce control output of box air conditioner, and the control output of fan will increase or reduce synchronously.
 
Interface 3: 
 
Display real rotational speed of inner fan and outer fan.
 
At manual mode of this interface, press buttons “▲,▼” can manually turn on/off control output of cabinet air conditioner.
 
Interface 4: 
 
Display temperature of inner coil and outer coil.
 
At manual mode of this interface, press buttons “▲,▼” can manually turn on/off control output of hydrogen exhaust.
 
Interface 5: 
 
Circularly display current alarms;
When multiple alarms occur, it will display each alarm information circularly.
 
(2)Parameter Mode:
 
At operating status, long press on the button ”PgDn” for around 3 seconds, or press the button ”PgUp” at interface 1, to enter parameter mode.The first entered interface is the main menu interface, see the following diagram.
 
TC06-40ZEH/01,400W,DC48V Air Conditioner,For Outdoor Telecom Cabinet/UPS Room/Base Station
Press the button “▲”, “▼” to choose corresponding parameter group; Press ”PgDn” to enter corresponding parameter group; Press ”PgUp” to return to operating mode. The parameters selection includes:
 
(a) Observation Parameter 
(b) Control Parameter Revision  
(c) Basic Parameter Revision 
(d) Manual/Auto Selection 
(e) Event Query 
(f) Return To Operating Mode 
 
(a)Observation Parameter Group (Apar):
 
Enter the interface to check some parameters which can’t be checked at operating mode, see “8.3.4 Parameter Instruction”. 
 
At parameter mode: on the left of line 1 is Parameter No. (PAnn); on the right of line 1 is parameter value. Line 2 shows the remark of the parameter.
 
(b) Control Parameter Group (CPar):
 
Enter the interface to observe or revise the parameters which can be revised, see “8.3.4 Parameter Instruction”. 
 
At parameter mode: on the left of line 1 is Parameter No. (PCnn), on the right of line 1 is parameter value. Line 2 shows the remark of the parameter.
 
(c) Basic Parameter Group (BPar): 
 
Enter the interface to observe or revise the parameters which can be revised, see “8.3.4 Parameter Instruction”. 
 
At parameter mode: on the left of line 1 is Parameter No. (PBnn), on the right of line 1 is parameter value. Line 2 shows the remark of the parameter.
 
(d) Manual Operation Parameter Group (A/M):
 
Enter the interface to select “Cool”, “Heater”, “Air”, “ToAuto” to conduct manual start and stop operation.
 
(e) Event Query (Query):
 
Enter query mode
 
8.3.4 Parameter Instruction
 
(1)Observation Parameters, PA00~PA13: 

Parameter No.

Parameter Name

Initial Value

Remark

PA00

Fr (air conditioner rotational speed)

 

compressor rotational speed

PA01

DI1 (digital input 1)

 

smoke sensor

PA02

DI2 (digital input 2)

 

door sensor

PA03

DI3 (digital input 3)

 

water sensor

PA04

DI4 (digital input 4)

 

other sensors 

PA05

DI5 (digital input 5)

 

reserve

PA06

DI6 (digital input 6)

 

reserve

PA07

DI7 (digital input 7)

 

low DC voltage 

PA08

ColRN (box air conditioner cooling start times)

 

times

PA09

ColRT (box air conditioner cooling time length)

 

0.1hour

PA10

HotRN (box air conditioner heating start times)

 

times

PA11

HotRT (box air conditioner heating time length)

 

0.1hour

PA12

ktRN (cabinet air conditioner heating start times)

 

times

PA13

ktRT(cabinet air conditioner heating time length)

 

0.1hour

(2) Control Parameters, PC00~PC24:

Parameter No.

Parameter Name

Initial Value

Remark

PC00

LOC (password parameter)

0

LOC=55, accessible to the following parameters

PC01

bacCol (box air conditioner control temperature)

25.0

 

PC02

bacHot (start heating temperature)

18.0

 

PC03

cacCol(cabinet air conditioner start temperature)

40.0

 

PC04

bacTb (box air conditioner control accuracy)

5.0

 

PC05

cacTb (cabinet air conditioner control hysteresis)

3.0

 

PC06

ehTd (hydrogen exhaust time interval)

24

Hour

PC07

ehTi (hydrogen exhaust time control)

5

Minute

PC08

lfTc (lack fluoride judgement limit)

0.5

°C

PC09

lfTd (lack fluoride judgement time length)

10

Minute

PC10

cacFZ (cabinet air conditioner over current threshold)

10.0

A

PC11

cacSTV (cabinet air conditioner status threshold)

0.5

A

PC12

bbTEH (temperature inside box for forced ventilation)

28.0

 

PC13

bbTPH (temperature inside box alarm high limit)

30.0

 

PC14

bbTPL (temperature inside box alarm low limit)

15.0

 

PC15

enTPH (temperature inside communication room alarm high limit)

35.0

 

PC16

enTPL (temperature inside communication room alarm low limit)

15.0

 

 

 

PC17

bbHPH (humidity inside box alarm high limit)

85

 

PC18

bbHPL (humidity inside box alarm low limit)

30

 

PC19

enHPH (humidity inside communication room alarm high limit)

90

 

PC20

enHPL (humidity inside communication room alarm low limit)

30

 

PC21

vp1Limit (inner coil temperature low limit)

0

protect when lower than the limit

PC22

vp2Limit (outer coil temperature high limit)

65.0

protect when higher than the limit

PC23

inFanOH (inner fan rotational speed limit)

100

Used to limit fan’s max rotational speed.

PC24

outFanOH (outer fan rotational speed limit)

100

(3) Basic Parameter, PB00~PB22:

 

Parameter No.

Parameter Name

Initial Value

Remark

PB00

LOC (password parameter)

0

LOC=55, accessible to the following parameters

PB01

hotEN (define heating device)

Forbid

 

PB02

ysjEN (compressor alarm allowed)

allow

When forbidden, it only alarms, but don’t stop.

PB03

fanEN (fan alarm allowed)

allow

When forbidden, it only alarms, but don’t stop.

PB04

bacDT (time interval between two starts of box air conditioner)

5

 

PB05

cacDT (time interval between two starts of cabinet air conditioner)

5

 

PB06

ADR(address)

1

 

PB07

BAUD(Baute Rate)

9600

 

PB08

CESel (CHA/ENG Select)

ENG

Chinese/English

PB09

bbBT (temperature inside box data compensation)

0.0

-20.0~20.0

PB10

enBT (communication room temperature data compensation)

0.0

-20.0~20.0

PB11

bbBH (humidity inside box data compensation)

0

-100~100

PB12

enBH  (communication room humidity data compensation)

0

-100~100

PB13

vpBT1 (inner coil temperature correction)

0.0

-20.0~20.0

PB14

vpBT2 (outer coil temperature correction)

0.0

-20.0~20.0

 

 

PB15

fanRC1 (fan 1 rotational speed coefficient)

30

 

PB16

fanRC2 (fan 2 rotational speed coefficient)

30

 

PB17

Year (year) 

real time

 

PB18

Month (month)

real time

 

PB19

Date (date)

real time

 

PB20

Hour (hour)

real time

 

PB21

Minute (minute)

real time

 

PB22

Second (second)

real time

 

8.4 Wiring Diagram

TC06-40ZEH/01,400W,DC48V Air Conditioner,For Outdoor Telecom Cabinet/UPS Room/Base Station

Diagram 4: Inner Terminals Wiring Diagram

JD1: main power supply input (DC48V);
JD2: heating control output;
JD4: fan control port:
        1- 48V; 2- inner fan control; 3- inner fan feedback;
        4- outer fan control; 5- outer fan feedback; 6- 0V.
JD5: direct ventilation (hydrogen exhaust) output port (48V);
JD6: DC compressor control port:
         connected with compressor control board control port. Please note the  direction.
JD7: alarm ouput port:
        1, 2: general alarm output dry contact;
        3, 4: air conditioner system alarm output.
JD8: 
       1, 2: remote control dry contact input;
       3, 4: working status output dry contact;
JD9: communication port:
        1: RXD (or 485A+);  2: TXD (or RS485B-);  3: SGND;
JD10: connected with four DI input. 
 
9. Maintenance
Maintenance Tools:
 
(1)Vacuum cleaner or compressed air cleaning agent 
(2)Soft brush
(3)Cross screwdriver
(4)Multimeter
(5)Clamp meter
(6)Digital thermometer
 
In order to keep normal temperature environment inside the cabinet, please conduct maintenance according to the “Maintenance Table”.
 
Maintenance Steps:
 
(1)Turn off the power.
(2)Disconnect the power line, and disconnect the signal line.
(3)Conduct maintenance according to the “Maintenance Table”.
(4)Connect the power line and signal line.
(5)Operating testing program. 
(6)Disconnect the power, restore the normal operating status.
(7)Connect the power.
(8)The equipment installation should reserve a maintenance space not less than 300mm.
 
 

Maintenance Table 

Check Items

Step Description

Maintenance Cycle 

Casing

Use brush or vacuum cleaner to clean the odds and ends on the casing.

6 months

Wiring

Check if it gets loose and if the power supply voltage is normal. 

6 months

Fans Abnormal

Move the fans to check if the rotation is smooth, and if there’s abnormal noise or odds and ends.

6 months

Cooling Fin

Use brush or vacuum cleaner to clean the dust on the cooling fin; use water or compressed air to clean the condenser.

 6 months

Water Drainage

Check if the water drainage pipe is smooth

1 year

Cooling/Heating

At normal operating status, the measured temperature difference between inside and outside temperatures is higher than 10°C.

1 year

Cable 

Check if cable peeling occurs. 

1 year

Communication Cable

Check if the cable includes hidden danger such as peeling. 

1 year

Grounding Cable 

Test if the equipment grounding  and cabinet grounding is normally connected, and the resistance is lower than 0.1Ω.

1 year

 