TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack

Certification
Good quality Two Compartments Outdoor Telecom Cabinet for sales
Good quality Two Compartments Outdoor Telecom Cabinet for sales
Timely response, professional skills, rigorous attitude, fast delivery, we are very satisfied, cooperation is very smooth.

—— Manish

From 1 sample to 45 sets, 76 sets, 200sets, we gradually established a strong trust. The cabinet quality is good and the design is reasonable.

—— Parmar

In the past three years, our cooperation is very cheerful, thanks for your company's technical support and patient service, the end user is very satisfied with the quality of outdoor telecom cabinet with cooling. Best wishes to our future cooperation.

—— Anthony

The air conditioner have been running for one and a half years. Cooling effective is good. Good after-sale service, and patiently instruct to use and solve technical problems. Environmental monitoring system is also running well, and remote monitoring the cabinet is very convenient.

—— Luis Alberto

I'm Online Chat Now

TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack

China TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack supplier
TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack supplier TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack supplier TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack supplier TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack supplier TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack supplier TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack supplier

Large Image :  TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack

Product Details:

Place of Origin: China
Brand Name: ESTEL
Certification: ISO9001:2008
Model Number: TC06-250JFH/01(KT044-60HZ)

Payment & Shipping Terms:

Minimum Order Quantity: 1 Set
Packaging Details: Wooden Case
Delivery Time: 10~15 Days
Payment Terms: T/T
Supply Ability: 80000 Sets Per Year
Contact Now
Detailed Product Description

AC220V 2500W 60Hz Air Conditioner
Model: TC06-250JFH/01
 
Foreword
The manual mainly includes TC06-250JFH/01 air conditioner’s application, technical parameters, operation instruction, product installation and maintenance, etc.
 
Note:
The manual only apply to TC06-250JFH/01 air conditioner. Our company reserves the right of final explanation of the content of this manual.
 
Any operation on this product must be performed by professional engineering and technical personnel.
 
 
Introduction
 
1. Introduction And Application Scope
 
TC06-250JFH/01 Air Conditioner is a full automation temperature control product. It uses intelligent controller to control the whole system of the air conditioner. According to the variation of environment temperature, the intelligent controller can automatically detect, operate and record the whole system’s operating time, power consumption, event and historical data. It can store 100 event records and 1280 historical data records, and can enquire 256 days’ daily record information. The product is widely applied in telecom cabinet, small and medium sized telecom room, UPS room, outdoor base station room, etc.
 
2. Features
 
(1) Strong adaptability
(2) High intelligence 
(3) High precision
(4) High reliability
(5) Low noise 
(6) Low energy consumption
(7) With 4 way switching value detection
(8) With 1 way room air conditioner control
(9) Voltage input range: 220VAC±15%  60Hz
(10) With dry contact alarm output 
 
3. System Principle Diagram
 
TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack
Diagram 1: System Principle Diagram
 
4. Standard Compliance
 
                                            Table 1 Standard Compliance

Standard

Description

GB/T 17626.7-1998

Electromagnetic compatibility

GB4706.1

Safety of household appliance and electrical appliance with similar use.

GB4798.1

Environmental conditions existing in the application for electric and electronic products - storage

GB4798.2

Environmental conditions existing in the application for electric and electronic products - transportation

GB4798.3

Environmental conditions existing in the application for electric and electronic products - usage

 

 

 

 

 

 

 

 

 

 

 

 

5. Technical Parameters
 

Environmental Performance

working environmental temperature

-20°C ~ 55°C

storage temperature

-40°C ~ 70°C

working humidity

≤95%

Thermal Performance

rated cooling capacity

2800W(L35 L35)

2600W(L25 L35)

heating input power

300W/500W (optional)

 

Electrical Performance

rated input current

4.8A(L35 L35)

4.6A(L25 L35)

rated input power

1056W(L35 L35)

1012W(L25 L35)

input voltage

AC220V

(185V~264V)

Noise

≤65dB

Reliability

MTBF

70000h

Refrigerant

R410A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack

 

Diagram 2:  Dimension of TC06-250JFH/01 Air Conditioner

 
6. Electrical Wiring Instruction
 
6.1 Electrical Wiring Diagram
TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack
Diagram 3: Electrical Wiring Diagram
 
Wiring Ports:
 
L  N  PE : power supply port (voltage input: 220VAC±15% 60Hz)
F+  F- : direct ventilation output port 
AL1  AL2: general alarm output port
A+  B-  SGND : RS485 communication port
N : not connected pi
 
8. System Control 
8.1 Function and Application
 
ET731 intelligent air conditioner controller is a universal intelligent controller, controlling with highly integrated STC SCM. It can intelligently control thermostatic cabinet air conditioner working and hydrogen exhausting, including functions such as fault self diagnosis, power-on self start, or restart after unexpected failure caused by other reasons. The controller is compatible with all types of air conditioners in the market.
 
The controller, with the features of advanced performance, easy installation and setting, are widely used in telecom cabinet, small and medium sized telecom room, UPS room, outdoor base station room, etc.
 
8.2 Technical Parameter
 
a. 2×16 Chinese/English shift LCD display, user friendly; 
b. Simultaneously display temperature and humidity inside the box and communication room temperature;    
c. Temperature measurement accuracy: 0.1 °C; humidity measurement accuracy:5%;
d. Can store 180 days’ daily event record, 1 record every day;
    Daily highest temperature, lowest temperature, average temperature
    Daily event record;
e. Save the former day’s daily data at 0:00 every day; Can query 180 days’ daily record information;
f. RS485 communication, YD/T 1363.1-2005 standard protocol, support remote detection and control;
g. Control mode: pulse (Non dry contact air conditioner), conducting (dry contact air conditioner)
h. Real-time control air conditioner on/off
i. Power supply: AC185V~264V/60HZ;
j. Power consumption:≤5W;
k. Working environment: -30°C~70°C; <90%RH;
l. Installation method: guide rail,hanging;
m. Dimension(L*W*H):150mm×190mm×45mm
 
8.3 Operating Instruction
 
ET731 uses English interfaces, which can be operated easily. All the operations can be realized with four buttons. The following is the control board diagram:
TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack
Diagram 4 Control Board Diagram
 
8.3.1 Buttons
 
PgDn:page down button, confirm button.      
Press once and release the button, page down;
A long press on the button, enter or exit parameter status;
At operating status: can select three display interfaces;
At parameter status: revise, confirm and parameter page down button; a long press on the button to exit parameter status.
 
▲:increasing parameter revision. Page down button for event query.  
 
▼:decreasing parameter revision. Page up button for event query.
 
PgUp: page up button; the function is oppose to PgDn operation.
 
8.3.2 Operating Interfaces 
 
The controller includes four types of working modes: operating mode, parameter mode, manual operating mode, and query mode.
 
(1) Operating Mode:
 
The mode is normal working mode. There are three operating interfaces which can be selected. The three interfaces display different content. When they are not selected, the interfaces will automatically shift. Press the button “PgDn” to select next display interface; press the button “PgUp” to select the previous display interface.   
 
Interface 1: 
TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack
 
Line 1: temperature and humidity inside the thermostatic box (or area I);
Line 2: box air conditioner status, real time clock;
------- cooling start sign;
☼  ------- heating start sign;
♂  ------- hydrogen exhaust /direct ventilation sign; 
--  ------- compressor/ heater stop working.  
 
Interface 2: 
 
 
TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack
Line 1: environment (or area II) temperature and humidity;
Line 2: inside and outside coil temperature display (T3, T4);
 
Interface 3: 
TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack
 
Circularly display current alarms;
 
When multiple alarms occur, it will display each alarm information circularly.
 
(2) Parameter Mode:
 
Function Menu:
(a) Observation Parameter 
(b) Control Parameter Revision 
(c) Basic Parameter Revision 
(d) Manual Operation 
(e) Event Query 
(f) Return To Operating Mode 
 
(a) Check operating parameters of key parts inside air conditioner, namely observation parameter. Operation steps:
 
TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack
Observation Parameter: on the left of line 1 is Parameter No. (PAnn); on the right of line 1 is parameter value. Line 2 shows the remark of the parameter.
 
(b) Revise operating parameters of air conditioner, namely control parameters. Operation steps:
TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack
Control Parameter: on the left of line 1 is Parameter No. (PCnn), on the right of line 1 is parameter value. Line
2 shows the remark of the parameter.
 
(c) Revise basic parameters of air conditioner. Operation steps:
TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack
Basic Parameter: on the left of line 1 is Parameter No. (PBnn), on the right of line 1 is parameter value. Line 2 shows the remark of the parameter.
 
(3) Manual Operation Mode:
 
Operation steps:
TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack
Enter the interface to select “Cool” (cooing), “Heater” (heating), “Air” (direct ventilation) to conduct manual start (ON) and stop (OFF) operation.
 
(4) Event Query Mode:
 
Operation steps:
TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack
 
8.4 Wiring Diagram
TC06-250JFH/01(KT044-60HZ), 2500W AC220V 60HZ Compressor Air Conditioner For Telecom Rack
 
Diagram 5: Wiring Diagram

Contact Details
TIANJIN ESTEL ELECTRONIC SCIENCE AND TECHNOLOGY CO., LTD

Contact Person: Ms. Fiona Liang

Tel: 86--13752765943

Send your inquiry directly to us (0 / 3000)