Product Details:
Payment & Shipping Terms:
|
|
Model |
STC-CPL4860ER |
||
|
Rated Capacity |
60A/2880W |
||
|
Input |
Rated Input Voltage |
220V AC |
|
|
AC Input Range |
90V-280V |
||
|
Max. Input Current |
17.8A |
||
|
AC Input Frequency |
45-66 Hz |
||
|
Power Factor |
≥0.99 |
||
|
Efficiency |
92% |
||
|
Output |
Rated Output Voltage |
48V DC |
|||
|
Output Voltage Range |
42-58V DC |
||||
|
Rated Output Current |
60A |
||||
|
Max. Output Power |
3600W |
||||
|
Load Output |
1 way load output |
||||
|
Battery Output |
1 way batery output |
||||
|
Battery LVD |
50A×1 |
||||
|
Wire Connection Mode |
front wiring connection |
||||
|
Rectifier Module |
STC-CPL4830RM |
||||
|
Monitoring Module |
STC-CPL-MC |
||||
|
Function |
Including RS485 Communicaiton Interface |
||||
|
Automatic current sharing |
|||||
|
The bus can realize parallel connection through current sharing. |
|||||
|
remote comtrol on/off |
|||||
|
hot-swappable |
|||||
|
dormancy energy saving function |
|||||
|
Environment |
Operating Temp. |
﹣40℃ - ﹢70℃ |
|||
|
Humidity |
≤95%, non-condensing |
||||
|
Protection Performance |
input over/under voltage protection |
||||
|
output over voltage protection |
|||||
|
output over current protection |
|||||
|
over temperature alarm and protection |
|||||
|
soft start function |
|||||
|
Safety Performance |
Input - output 3000VAC/10mA/1min, no arc, no break down. |
||||
|
Input - output 2500VAC/10mA/1min, no arc, no break down. |
|||||
|
Output-cabinet 500VAC/10mA/1min no arc, no break down. |
|||||
|
Weight (Kg) |
≤6KG (including rectifier modules) |
||||
|
Dimension |
44mm (H)×482.6mm (W)×255mm (D) |
||||