Product Details:
Payment & Shipping Terms:
|
Material: | Galvanized Steel | Color: | Grey (support Custom Made) |
---|---|---|---|
Coating: | Anti-corrosion Outdoor Powder Coating | Heat Insulation: | PEF |
External Size: | H×W×D 2000×800×800mm | Structure: | Sandwich Structure, Double Wall, With Insulation |
Cabinet Lock: | Anti-theft Three Point Lock | Protection Level: | IP65 |
Cable Entry: | At Cabinet Bottom | Grounding Protection: | Copper Bar |
Cooling: | AC110V Air Conditioner And DC48V Fans | Accessories Options: | PDU,environment Monitoring System |
Product Description
IP65 Thermostatic 19" Equipment Outdoor Telecom Enclosure / Environment Monitoring System
Quick Details
Place of Origin: Shenzhen, China (Mainland) | External Size H×W×D 2000×800×800mm |
Brand Name: ESTEL |
Structure: double wall, with insulation, sandwich structure. |
Model Number: ET8080200 |
Cabinet Layout: one compartment, for installing 19” equipment |
Product Name: Outdoor Telecom Equipment Cabinet |
Cabinet Lock: anti-theft three point lock |
Certification: ISO9001, CE, 3C, FCC, TLC, IP65 |
Protection Level: IP65 |
Application: outdoor telecom base station | Cable Entry: at cabinet bottom |
Material: galvanized steel | Illumination: DC48V LED lamp |
Heat Insulation: PEF |
Grounding Protection: copper bar |
Color: grey (support custom made) |
Cooling: AC110V Air Conditioner and DC48V fans |
Coating: anti-corrosion outdoor powder coating |
Accessories Options: PDU,environment monitoring system |
Payment & Shipping Terms
Minimum Order Quantity: | 1 set |
Price: | negotiation |
Payment Terms: | L/C,D/A,T/T, Western Union, Paypal, etc |
Supply Ability: | 7,500 sets per month |
Delivery Time: | 10-15 working days |
Packaging Details: | wooden case |
1. Specifications
(1) Technical Parameters
Item | Type | Technical Parameter |
Structure | Dimension | External Size H×W×D 2000×800×800mm |
Layout | One compartment | |
Equipment Installation Method | 19” standard rack | |
Door | With one front door, and anti-theft three point lock for outdoor cabinet (support padlock) | |
Material |
1.Galvanized steel; 2.Double wall, thickness of outer plate: 1.5mm, thickness of inner plate: 0.8mm, with 20mm heat insulation between two walls. |
|
Structure | Assembled | |
Ingress Protection | IP65 | |
Temperature Control | Cooling | AC110V 60Hz 1500W Air Conditioner and DC48V fans |
Lighting | LED lamp | 48V LED lamp |
Temperature | Temperature | Working Temperature: -40°C ~ +55°C |
Storage Temperature: -50°C ~ + 70°C | ||
Transport Temperature: -50°C ~ +70°C | ||
Humidity | Relative Humidity | 5% ~ 100% |
Pressure | Air Pressure | 62kpa ~ 101kpa (similar to 0m ~ 5000m altitude) |
Radiation Intensity | Solar Radiation Intensity | 1124 × (1±5%)W/m2 |
(2) Accessories List
No. | Item | Quantity | Unit | Specs |
1 | Outdoor Telecom Cabinet | 1 | Set |
(1) External Size H×W×D 2000×800×800mm (2) One compartment; (3) With one front door; with anti-theft three point lock for outdoor cabinet (support padlock) (4) Material: galvanized steel; double walls, thickness of outer plate: 1.5mm, thickness of inner plate: 0.8mm, with 20mm heat insulation between two walls |
2 | Air Conditioner | 1 | Set |
Power Supply: AC110V, 60Hz Cooling Capacity: 1500W Model: TC06-150JFH/01 |
3 | Fans | 2 | PC | 12038, DC48V |
4 | Power Distribution Unit | 1 | Set |
Grade B Lightning Proof AC Input: 63A/2P *1; AC Output: 16A/1P*4; DC Output: 16A/1P*4. Height: 4U |
5 | Environment Monitoring System | 1 | Set |
1× environment monitoring unit; 1× smoke sensor, 1×water sensor, 1× temperature&humidity sensor, 2× door sensor. |
6 | LED Lamp | 1 | Pc | DC48V |
7 | Package | 1 | Set | Wooden Case |
The Outdoor Telecom Cabinet is mainly used in communication base station, such as 4G system, communication/network integrated service, access/transmission switching station, emergency communication/transmission, etc.
The cabinet is made of galvanized steel, with double walls, thickness of outer plate: 1.5mm, thickness of inner plate: 0.8mm. There are heat insulation between inner wall and outer wall. The insulation material is 20mm PEF. The cabinet is assembled type.
The cabinet is equipment cabinet, including 19” equipment installation rack, with air conditioner on cabinet door.
The cabinet door uses embedded structure. The door opening angle is larger than 110°and the door limit device can limit the opening angle. The lock is theftproof three point lock, supporting padlock. Each cabinet door include open door sensor, working together with the environment monitoring unit.
4.1 The cabinet is dustproof, sunproof and rainproof, which is used in outdoor environment.
4.2 The cabinet cooling uses air conditioner.
4.3 Including -48VDC illumination lamp.
4.4 The cabinet includes power and environment monitoring unit, which can send power failure alarm, door open alarm, temperature and humidity alarm, smoke alarm, water alarm etc.
4.5 The layout of the cabinet is reasonable, which will facilitate cable access, fixing and grounding. At the bottom of the cabinet, there are entrance holes individually for power cable, signal cable and optical cable.
4.6 All the cables, sealing and heat insulation used in the cabinet are made from flame retardant materials.
4.7 The cabinet includes 19” standard installation rack.
Operating temperature: -40°C ~ + 45°C
Storage temperature: -25°C ~ + 55°C
Transport temperature: -40°C ~ + 70°C
Relative humidity (RH): 5%~99%
Air pressure: 62kPa ~ 101kPa (similar to 0m ~ 5000m altitude)
Dimension Diagram
Cabinet External Dimension (W×D×H): 800×800×2000mm.
6.1 LED lamp, smoke sensor and door sensor are installed at the top of the cabinet. Environment monitoring unit and PDU are installed on 19” rack.
6.2 Water sensor is installed at the bottom of the cabinet.
6.3 Temperature and humidity sensor is installed at the side inside the cabinet.
6.4 Air Conditioner is installed on the door of the cabinet.
Feeder cable and other external cables all use bottom wiring method.
Cabinet surface coating is outdoor special powder coating, with white gray color (PANTONE 428C). The coating complies with GB/T 3181-2008 requirement.
10.1 Position of installation holes at cabinet base are as follows:
Diagram 1
10.2 Users prefabricate concrete base.
10.3 Pre-embed 4pcs M10×120 anchor bolts on the concrete base. Distance between bolts are as that in diagram 1. Bolt exposed height is 40mm. Put the cabinet on the concrete base, align anchor bolts, then screw on nuts, and tighten them with wrench.
10.4 According to site situation, put the cabinet on the concrete base with forklift, crane or manually, and fix it on the concrete base with bolts.
11. Packing and Shipping
Our Delivery Agent
The goods can be shipped by sea, by air, by courier, by land, by train, etc.
Besides the following delivery agent, we can also look for the delivery agent with the best price in china if you need us to do for you.
12. Our Contact Information
Mobile Phone: 0086-13752765943
Telephone: 0086-0755 66600941
Email: info@estel.com.cn
lxf.estel@hotmail.com
Skype: fiona.liang10