500W DC48V AIR CONDITIONER
Model: TC06-50ZEH/01
1. Introduction
Diagram 1: System Principle Diagram
4. Standard Compliance
Standard |
Description |
GB/T 17626.7-1998 |
Electromagnetic compatibility |
GB4706.1 |
Safety of household appliance and electrical appliance with similar use. |
GB4798.1 |
Environmental conditions existing in the application for electric and electronic products - storage |
GB4798.2 |
Environmental conditions existing in the application for electric and electronic products - transportation |
GB4798.3 |
Environmental conditions existing in the application for electric and electronic products - usage |
5. Technical Parameters
Model No. |
TC06-50ZEH/01 |
|
Environmental Performance |
working environmental temperature |
-20°C ~ 55°C |
storage working temperature |
-40°C ~ 70°C |
|
working humidity |
≤95% |
|
Thermal Performance |
rated cooling capacity |
600W(L35 L35) 500W(L25 L35) |
heating input power |
no |
|
Electrical Performance |
rated input current |
3.5A(L35 L35) 3.3A(L25 L35) |
rated input power |
168W(L35 L35) 158W(L25 L35) |
|
input voltage |
DC48V |
|
Reliability |
MTBF |
60000 hours |
Noise |
≤65dB |
Diagram 2: Dimension Diagram
6. Installation and Electrical Wiring
Tools Name |
Function |
Cross Screwdriver |
Fix air conditioner. |
Small Slotted Screwdriver |
Wire power supply port on the panel |
Wire Stripper |
Wire stripping |
Wire Crimper |
Crimp power supply for equipment |
Multimeter |
Check the wiring to ensure it’s correctly connected and without short circuit. |
Clamp Meter |
Test operating current of the air conditioner |
Parameter No. |
Parameter Name |
Initial Value |
Remark |
PA00 |
Fr (air conditioner rotational speed) |
|
compressor rotational speed |
PA01 |
DI1 (digital input 1) |
|
smoke sensor |
PA02 |
DI2 (digital input 2) |
|
door sensor |
PA03 |
DI3 (digital input 3) |
|
water sensor |
PA04 |
DI4 (digital input 4) |
|
other sensors |
PA05 |
DI5 (digital input 5) |
|
reserve |
PA06 |
DI6 (digital input 6) |
|
reserve |
PA07 |
DI7 (digital input 7) |
|
low DC voltage |
PA08 |
ColRN (box air conditioner cooling start times) |
|
times |
PA09 |
ColRT (box air conditioner cooling time length) |
|
0.1hour |
PA10 |
HotRN (box air conditioner heating start times) |
|
times |
PA11 |
HotRT (box air conditioner heating time length) |
|
0.1hour |
PA12 |
ktRN (cabinet air conditioner heating start times) |
|
times |
PA13 |
ktRT(cabinet air conditioner heating time length) |
|
0.1hour |
(2) Control Parameters, PC00~PC24:
Parameter No. |
Parameter Name |
Initial Value |
Remark |
PC00 |
LOC (password parameter) |
0 |
LOC=55, accessible to the following parameters |
PC01 |
bacCol (box air conditioner control temperature) |
25.0 |
|
PC02 |
bacHot (start heating temperature) |
18.0 |
|
PC03 |
cacCol(cabinet air conditioner start temperature) |
40.0 |
|
PC04 |
bacTb (box air conditioner control accuracy) |
5.0 |
|
PC05 |
cacTb (cabinet air conditioner control hysteresis) |
3.0 |
|
PC06 |
ehTd (hydrogen exhaust time interval) |
24 |
Hour |
PC07 |
ehTi (hydrogen exhaust time control) |
5 |
Minute |
PC08 |
lfTc (lack fluoride judgement limit) |
0.5 |
°C |
PC09 |
lfTd (lack fluoride judgement time length) |
10 |
Minute |
PC10 |
cacFZ (cabinet air conditioner over current threshold) |
10.0 |
A |
PC11 |
cacSTV (cabinet air conditioner status threshold) |
0.5 |
A |
PC12 |
bbTEH (temperature inside box for forced ventilation) |
28.0 |
|
PC13 |
bbTPH (temperature inside box alarm high limit) |
30.0 |
|
PC14 |
bbTPL (temperature inside box alarm low limit) |
15.0 |
|
PC15 |
enTPH (temperature inside communication room alarm high limit) |
35.0 |
|
PC16 |
enTPL (temperature inside communication room alarm low limit) |
15.0 |
|
PC17 |
bbHPH (humidity inside box alarm high limit) |
85 |
|
PC18 |
bbHPL (humidity inside box alarm low limit) |
30 |
|
PC19 |
enHPH (humidity inside communication room alarm high limit) |
90 |
|
PC20 |
enHPL (humidity inside communication room alarm low limit) |
30 |
|
PC21 |
vp1Limit (inner coil temperature low limit) |
0 |
protect when lower than the limit |
PC22 |
vp2Limit (outer coil temperature high limit) |
65.0 |
protect when higher than the limit |
PC23 |
inFanOH (inner fan rotational speed limit) |
100 |
Used to limit fan’s max rotational speed. |
PC24 |
outFanOH (outer fan rotational speed limit) |
100 |
(3) Basic Parameter, PB00~PB22:
Parameter No. |
Parameter Name |
Initial Value |
Remark |
PB00 |
LOC (password parameter) |
0 |
LOC=55, accessible to the following parameters |
PB01 |
hotEN (define heating device) |
Forbid |
|
PB02 |
ysjEN (compressor alarm allowed) |
allow |
When forbidden, it only alarms, but don’t stop. |
PB03 |
fanEN (fan alarm allowed) |
allow |
When forbidden, it only alarms, but don’t stop. |
PB04 |
bacDT (time interval between two starts of box air conditioner) |
5 |
|
PB05 |
cacDT (time interval between two starts of cabinet air conditioner) |
5 |
|
PB06 |
ADR(address) |
1 |
|
PB07 |
BAUD(Baute Rate) |
9600 |
|
PB08 |
CESel (CHA/ENG Select) |
ENG |
Chinese/English |
PB09 |
bbBT (temperature inside box data compensation) |
0.0 |
-20.0~20.0 |
PB10 |
enBT (communication room temperature data compensation) |
0.0 |
-20.0~20.0 |
PB11 |
bbBH (humidity inside box data compensation) |
0 |
-100~100 |
PB12 |
enBH (communication room humidity data compensation) |
0 |
-100~100 |
PB13 |
vpBT1 (inner coil temperature correction) |
0.0 |
-20.0~20.0 |
PB14 |
vpBT2 (outer coil temperature correction) |
0.0 |
-20.0~20.0 |
PB15 |
fanRC1 (fan 1 rotational speed coefficient) |
30 |
|
PB16 |
fanRC2 (fan 2 rotational speed coefficient) |
30 |
|
PB17 |
Year (year) |
real time |
|
PB18 |
Month (month) |
real time |
|
PB19 |
Date (date) |
real time |
|
PB20 |
Hour (hour) |
real time |
|
PB21 |
Minute (minute) |
real time |
|
PB22 |
Second (second) |
real time |
|
8.4 Wiring Diagram
Diagram 4: Inner Terminals Wiring Diagram
Maintenance Table
Check Items |
Step Description |
Maintenance Cycle |
Casing |
Use brush or vacuum cleaner to clean the odds and ends on the casing. |
6 months |
Wiring |
Check if it gets loose and if the power supply voltage is normal. |
6 months |
Fans Abnormal |
Move the fans to check if the rotation is smooth, and if there’s abnormal noise or odds and ends. |
6 months |
Cooling Fin |
Use brush or vacuum cleaner to clean the dust on the cooling fin; use water or compressed air to clean the condenser. |
6 months |
Water Drainage |
Check if the water drainage pipe is smooth |
1 year |
Cooling/Heating |
At normal operating status, the measured temperature difference between inside and outside temperatures is higher than 10°C. |
1 year |
Cable |
Check if cable peeling occurs. |
1 year |
Communication Cable |
Check if the cable includes hidden danger such as peeling. |
1 year |
Grounding Cable |
Test if the equipment grounding and cabinet grounding is normally connected, and the resistance is lower than 0.1Ω. |
1 year |