Product Details:
Payment & Shipping Terms:
|
■ Small scale program controlled exchanges
■ Access network
■ Transmission equipment
■ Mobile communication
■ Satellite communication ground station
■ Microwave communication
Configuration |
Rectifier Module |
Monitoring Module |
Distribution |
Remark |
Standard |
STC-CPL4850RM |
STC-CPL-MA (With Ethernet Port) |
AC distribution: 3-phase, 4-wire input, 4-pole AC breaker @ general line (32A); DC distribution: Battery fuse 100A×2; LVLD: 32A×4 16A×2 10A×2 LVBD: 63A×2 |
For details, please refer to the specifications of modules. |
Environment |
|||||
Item |
Min. |
Typical |
Max. |
Unit |
Remark |
Operating temperature |
-25 |
|
55 |
°C |
When ≥55°C, decreased power output |
Storage temperature |
-40 |
|
80 |
°C |
|
Humidity |
10 |
|
90 |
% |
Relative humidity without condensing |
Atmospheric pressure |
70 |
|
106 |
KPa |
|
Altitude |
0 |
|
3000 |
m |
|
Cooling |
Forced cooling with fan |
Input |
|||||
Item |
Min. |
Typical |
Max. |
Unit |
Remark |
Input voltage range |
90 |
220 |
290 |
Vac |
|
Input frequency |
45 |
50 |
65 |
Hz |
|
Input current |
|
|
20 |
A |
|
Power factor |
0.98 |
|
|
|
Rated load |
Input over voltage protection |
300 |
|
|
Vac |
Automatically recoverable |
Input over voltage recovery |
290 |
|
|
Vac |
Return difference ≥5V |
Input under voltage protection |
|
|
85 |
Vac |
Automatically recoverable |
Input under voltage recovery |
|
|
90 |
Vac |
Return difference ≥5V |
Input over current protection |
|
|
|
|
MCB in AC Input supplied protection |
Output |
|||||
Item |
Min. |
Typical |
Max. |
Unit |
Remark |
Output voltage range |
42 |
53.5 |
58 |
Vdc |
Adjustable by monitor, tested in no load |
Output power |
|
8000 |
|
W |
Make sure rated 4800W output when input voltage is 176~290VAC (rated power includes battery power plus load power) |
|
4000 |
|
W |
150~175VAC input |
|
|
2000 |
|
W |
90~150VAC input |
|
Output over voltage protection |
58.5 |
|
60.5 |
Vdc |
Lock up |
Output current limiting protection |
|
|
|
|
Current limiting protection |
Output short circuit protection |
|
|
|
|
Long-term short circuit protection, automatically recoverable |
Over temperature protection |
|
|
|
|
Automatically recoverable in normal temperature 65℃ |
Battery power-down protection |
|
|
|
|
Battery power-down protection |
Battery polarities reversal connection protection |
|
|
|
|
No damage on battery and power system |
Voltage withstand efficiency |
|
|
±1 |
% |
|
Normal Parameters |
|||||
Item |
Min. |
Typical |
Max. |
Unit |
Remark |
Temperature coefficient |
|
|
±0.2 |
‰/℃ |
|
Current sharing unbalance |
|
|
±5 |
% |
Within 50~100%load range |
Start-up/shunt-down overshoot range |
|
|
±5 |
% |
Any module is removed when operating, (the load current should be less than total output current), the system output voltage fluctuates |
Dynamic response recovery time |
|
|
200 |
uS |
25%~50%~25% load variation 50%~75%~50% load variation |
Dynamic response overshoot |
|
|
±5 |
% |
Rated output voltage, rated load current |
Efficiency |
90 |
92 |
|
% |
220Vac input, rated input voltage, rated load current |
83 |
|
|
% |
110Vac input, rated output voltage, rated load current |
|
Start-up time |
3 |
|
8 |
S |
pre-current limiting is fitted with start-up output between rated start up input voltage and rated output voltage established period |
Pressure drop |
|
|
500 |
mV |
|
Peak-peak noise voltage |
|
|
200 |
mV |
|
Psophometrically weighted noise voltage |
|
|
2 |
mV |
|
Other Parameters |
|
Item |
Requirement |
Acoustic noise |
≤55dB(A) |
Smelling |
any abnormal and poisonous smelling is not allowed |
Components |
rated temperature of the electrolytic capacitor ≥105℃ |
Hot swappable |
the rectifier module meets the hot-swappable requirement |
Mixed insertion |
rectifier modules can mixed insertion |
Ineffective separation |
rectifier module can separate with system when it is ineffective |
Cooling |
Forced cooling by fan mounted on rectifier, face in, back out. The fan is mounted on rectifier front panel; can be disassembled. Fan speed and temperature can be controlled by user |
Insulation Rating |
|||||
Parameters |
Min. |
Typical |
Max. |
Unit |
Remark |
Input-chassis |
|
750 |
|
Vdc |
|
Input-output |
|
1414 |
|
Vdc |
|
Output-chassis |
|
750 |
|
Vdc |
|
Insulating Resistance |
relative humidity is 90%, |
3. Mechanical Properties
Mechanical specifications |
|
Dimensions (Overall) |
482.6*350*219.3mm |
Weight(kg)(Overall) |
≤(Inclusive of module) ≤( Frame + Distribution, exclusive of module) |
Item |
Sign |
AWG/ Min. section(#/mm2) |
AWG / Max. section(#/mm2) |
Temp rating(℃) |
Withstand voltage (V) |
Output load wire |
Load1, Load1-, Load2, Load2- |
12#/4 |
10#/5.5 |
105 |
600 |
Output load wire |
Load3, Load3- Load4, Load4- |
6#/10 |
4#/16 |
105 |
600 |
Input GND wire |
PEin |
9#/6 |
6#/10 |
105 |
600 |
Mains neutral wire |
Nin |
6#/10 |
4#/16 |
105 |
600 |
Mains live wire |
Lin |
6#/10 |
4#/16 |
105 |
600 |
Battery + |
(BATT +) |
2#/35 |
1#/50 |
105 |
600 |
Battery - |
(BATT -) |
2#/35 |
1#/50 |
105 |
600 |
Output load wire |
Load1, Load1-, Load2, Load2- |
12#/4 |
10#/5.5 |
105 |
600 |
Contactor NO. |
Terminal type |
I/O |
Signal function |
Other panel, contact and signal connected |
Remark |
J2 |
AC voltage(A phase)detection |
I |
AC voltage(A phase)signal input |
AC A phase voltage |
None |
J3 |
AC SPD alarm signal |
I |
AC PSD alarm signal input |
AC PSD connection alarm signal |
None |
J4 |
Battery conactor control signal |
0 |
Battery contactor control signal output |
Connection between cable and contactor coil |
Installation requirement marked on coil terminal of sample signal |
J5 |
Battery current sharing interface |
I |
Battery current sharing sample signal input |
Cable connection current sharing sample signal |
Cable of sample signal includes positive and negtive ones |
J6 |
Load contactor control signal interface |
O |
Load contactor control signal output |
Cable connection contactor control coil |
Installation requirement marked on coil terminal of sample signal |
J7 |
Load current sharing signal interface |
I |
Load current sharing sample signal input |
Sample signal of cable connection current sharer |
Cable of sample signal includes positive and negative ones |
CON8 |
Load and battery output signal detection terminal |
I |
Load and battery signal detection input |
None |
Attention: D1-D2 battery D3-D14 load |
CON1 CON2 CON3 |
Rectifier module interface |
I/O |
Rectifier signal input and output, rectifier power output |
None |
None |
CON7 |
PMU 96PIN connector |
I/O |
Monitor signal input and output |
Terminal connects with PMU |
None |
6. STC-CPL48150ER Distribution Frame
7.1 Monitor Module Function
Function |
Remark |
Remote monitoring of the host |
The host can conduct enquiries, settings and control upon the monitoring and realize the remote message, remote sense and remote control. |
Rectifier management by monitoring module |
To send controlling orders to or get data from the rectifier module via RS485 communication. |
Battery management |
To manage the low voltage, power down, equalizing/float charge, temperature compensation and capacity testing of the battery. |
Output management by monitoring module |
To inspect and control the system |
LED indicator |
Signal indication |
6 dry contacts output |
Stem nodes setting |
COM port signal |
RS232 |
LCD display |
to conduct setting and modification on the menu |
For details, please refer to specifications of “GPE 48150D”. |
7.2 PC Software
Item |
Unit |
Min. |
Typical |
Max. |
Testing conditions |
AC Input Voltage |
Vac |
90 |
220 |
290 |
|
AC input voltage frequency |
Hz |
45 |
50 |
65 |
Rated load |
Input power factor |
|
0.99 |
|
|
Rated voltage/rated load |
Output voltage range |
Vdc |
44 |
53.5 |
58 |
|
Output current |
A |
0 |
50 |
|
176~290V AC input |
A |
0 |
22 |
|
90~175V AC input |
|
Output voltage withstand regulation |
|
|
|
±1% |
|
Peak-peak value Vp-p |
mV |
|
|
200 |
Tested with each of 0.1uF ceramic capacitor and 10uF electrolytic capacitor with 20MHzband width. |
Output power |
W |
0 |
2900 |
|
When 176Vac~290Vac input, 2900W output is met with |
W |
0 |
1200 |
|
90Vac~175Vac input |
|
Output efficiency |
% |
92 |
93 |
|
220V AC input (1. when input voltage is 220Vac, rated output voltage, 25% above rated output voltage. 2. up to 94%) |
% |
86 |
|
|
110V AC input |
|
Input over voltage protection |
Vdc |
300 |
|
|
Automatically recoverable |
Input over voltage protection recovery point |
Vdc |
290 |
|
|
|
Input under voltage protection |
Vdc |
|
|
85 |
Automatically recoverable |
Input under voltage protection recovery point |
Vdc |
|
|
90 |
|
Output over voltage protection point |
V |
58.5 |
59 |
60.5 |
1. module internal failure will result in over voltage and module itself locked up 2. when external voltage above over voltage protection point is added, module works normally. |
Output current limiting protection |
A |
54 |
|
|
Automatically recoverable |
Short circuit protection |
A |
long-term short circuit is available, automatically recoverable |
|||
Over temperature protection |
|
Automatically recoverable under 65℃ ambient temperature |
|||
The detailed information is listed in GPR4850D rectifier specification |