Product Details:
Payment & Shipping Terms:
|
AC220V, 1600W Air Conditioner
1. Description
Standard |
Description |
GB/T 17626.7-1998 |
Electromagnetic compatibility |
GB4706.1 |
Safety of household appliance and electrical appliance with similar use. |
GB4798.1 |
Environmental conditions existing in the application for electric and electronic products - storage |
GB4798.2 |
Environmental conditions existing in the application for electric and electronic products - transportation |
GB4798.3 |
Environmental conditions existing in the application for electric and electronic products - usage |
5.Technical Parameters
Environmental Performance |
working environmental temperature |
-20°C ~ 55°C |
storage working temperature |
-50°C ~ 70°C |
|
working humidity |
≤95% |
|
Thermal Performance |
rated cooling capacity |
1600W(L25 L35) 1500W(L35 L35) |
heating input power |
300(optional) |
|
Electrical Performance |
rated input current |
2.15A(L25 L35) 2.35A(L35 L35) |
rated input power |
473W(L25 L35) 517W(L35 L35) |
|
input voltage |
AC220V/50Hz (187V ~ 264V) |
Diagram 2: Dimension Diagram
Tools Name |
Function |
Cross Screwdriver |
Fix air conditioner. |
Small Slotted Screwdriver |
Wire power supply port on the panel |
Wire Stripper |
Wire stripping |
Wire Crimper |
Crimp power supply for equipment |
Multimeter |
Check the wiring to ensure it’s correctly connected and without short circuit. |
Clamp Meter |
Test operating current of the air conditioner |
Parameter No. |
Parameter Name |
Initial Value |
Remark |
PA00 |
Vac (mains power supply voltage) |
|
V |
PA01 |
Icomp (compressor current feedback) |
|
fan state monitoring |
PA02 |
Ifan1 (inner fans current feedback) |
|
non-adjustable speed fan |
PA03 |
Ifan2 (outer fans current feedback) |
|
|
PA04 |
InFr (inner circulation fans rotation speed) |
|
adjustable speed fan |
PA05 |
OutFr (outer circulation fans rotation speed) |
|
|
PA06 |
DI1 (digital input 1) |
|
door alarm sensor |
PA07 |
DI2 (digital input 2) |
|
compressor pressure alarm |
PA08 |
DI3 (digital input 3) |
|
smoke sensor |
PA09 |
DI4 (digital input 4) |
|
water sensor |
PA10 |
ColRN (box air conditioner cooling start times) |
|
times |
PA11 |
ColRT (box air conditioner cooling time length) |
|
0.1hour |
PA12 |
HotRN (box air conditioner heating start times) |
|
times |
PA13 |
HotRT (box air conditioner heating time length) |
|
0.1hour |
Control Parameters, PC00~PC17:
Parameter No. |
Parameter Name |
Initial Value |
Remark |
PC00 |
LOC (password parameter) |
0 |
LOC=55, accessible to the following parameters |
PC01 |
colTa (box air conditioner cooling start temperature) |
25.0 |
|
PC02 |
colTb (cooling control return difference) |
2.0 |
|
PC03 |
hotTa (box air conditioner heating start temperature) |
10.0 |
|
PC04 |
hotTb (heating control return difference) |
5.0 |
|
PC05 |
ZFanTa (forced ventilation start temperature) |
35.0 |
|
PC06 |
ZFanTb (forced ventilation control return difference) |
2.0 |
|
PC07 |
TPH (inner temperature alarm upper limit) |
30.0 |
|
PC08 |
TPL (inner temperature alarm lower limit) |
10.0 |
|
PC09 |
compST (compressor status threshold) |
1.0 |
Unit: A. In case of working, when the feedback current is lower than status threshold or higher than fault threshold, it will be treated as fault and output accordingly. |
PC10 |
compFZ (compressor fault threshold) |
10.0 |
|
PC11 |
fanST (fans status threshold) |
0.25 |
|
PC12 |
fanFZ (fans fault threshold) |
2.0 |
|
PC13 |
pqTd (automatic hydrogen exhaust cycle) |
24 |
Unit: hour |
PC14 |
pqTi (hydrogen exhaust time length) |
5 |
Unit: minute |
PC15 |
Tprotect (compressor protection operation environment temperature) |
55.0 |
°C |
PC16 |
inFanOH (inner fans speed limit) |
100 |
|
PC17 |
outFanOH (outer fans speed limit) |
100 |
|
Basic Parameter, PB00~PB17:
Parameter No. |
Parameter Name |
Initial Value |
Remark |
PB00 |
LOC (password parameter) |
0 |
LOC=55, accessible to the following parameters |
PB01 |
inBT (inside box temperature data compensation) |
0.0 |
|
PB02 |
outBT (communication room temperature data compensation) |
0.0 |
|
PB03 |
FaultEN (fault operation definition allowed) |
Forbid |
When allowed, it can operate without feedback. |
PB04 |
hotDef (define heating device) |
Forbid |
|
PB05 |
fanDef (fan definition) |
non-adjustable speed |
Non-adjustable speed, adjustable speed, inner fan with non-adjustable speed and outer fan with adjustable speed. |
PB06 |
VacX (mains power supply display correction coefficient) |
1.00 |
When the display deviates from the real value, correct scale. Display Value = Real Value × Coefficient. |
PB07 |
IcompX (air conditioner current display correction) |
1.00 |
|
PB08 |
fanX (fan feedback current correction coefficient) |
1.00 |
|
PB09 |
ADR(address) |
1 |
|
PB10 |
BAUD(Baute Rate) |
9600 |
|
PB11 |
CESel (Select English or Chinese) |
English |
|
PB12 |
Year (year) |
real time |
|
PB13 |
Month (month) |
real time |
|
PB14 |
Date (day) |
real time |
|
PB15 |
Hour (hour) |
real time |
|
PB16 |
Minute (minute) |
real time |
|
PB17 |
Second (second) |
real time |
|
10.Wiring Diagram
Diagram 5: Wiring Diagram
11.Maintenance
Check Items |
Step Description |
Maintenance Cycle |
Casing |
Use brush or vacuum cleaner to clean the odds and ends on the casing. |
6 months |
Wiring |
Check if it gets loose and if the power supply voltage is normal. |
6 months |
Fans Abnormal |
Move the fans to check if the rotation is smooth, and if there’s abnormal noise or odds and ends. |
6 months |
Cooling Fin |
Use brush or vacuum cleaner to clean the dust on the cooling fin; use water or compressed air to clean the condenser. |
6 months |
Water Drainage |
Check if the water drainage pipe is smooth |
1 year |
Cooling/Heating |
At normal operating status, the measured temperature difference between inside and outside temperatures is higher than 10°C. |
1 year |
Cable |
Check if cable peeling occurs. |
1 year |
Communication Cable |
Check if the cable includes hidden danger such as peeling. |
1 year |
Grounding Cable |
Test if the equipment grounding and cabinet grounding is normally connected, and the resistance is lower than 0.1Ω. |
1 year |
Failures
Failure |
Analysis |
Air conditioner doesn’t work |
Without power input or internal power line may peel. |
Temperature failure alarm |
The temperature probe terminal may be loose, or the probe doesn’t work. |
Fans don’t rotate. |
Check if the power supply is normal, if the cables peels or fan blades are blocked by odds and ends. |
Fans have abnormal noise. |
fan blades are interfered by odds and ends, or fans are damaged. |
Can’t drain condensated water. |
The water drainage pipe is blocked. |