1. Introduction And Application Scope
Diagram 1: System Principle Diagram
4. Standard Compliance
Table 1 Standard Compliance
Standard |
Description |
GB/T 17626.7-1998 |
Electromagnetic compatibility |
GB4706.1 |
Safety of household appliance and electrical appliance with similar use. |
GB4798.1 |
Environmental conditions existing in the application for electric and electronic products - storage |
GB4798.2 |
Environmental conditions existing in the application for electric and electronic products - transportation |
GB4798.3 |
Environmental conditions existing in the application for electric and electronic products - usage |
CE |
Third party certificate |
Environmental Performance |
working environmental temperature |
-20°C ~ 55°C |
storage temperature |
-40°C ~ 70°C |
|
working humidity |
≤95% |
|
Thermal Performance |
rated cooling capacity |
350W(L35 L35) 300W(L25 L35) |
heating input power |
500W (optional) |
|
Electrical Performance |
rated input current |
0.9A(L35 L35) 0.7A(L25 L35) |
rated input power |
198W(L35 L35) 154W(L25 L35) |
|
input voltage |
AC220V/50Hz (185V~264V) |
Diagram 2: Dimension of 300W 220VAC Air Conditioner
6. Installation and Electrical Wiring Instruction
Tools Name |
Function |
Cross Screwdriver |
Fix air conditioner. |
Small Slotted Screwdriver |
Wire power supply port on the panel |
Wire Stripper |
Wire stripping |
Wire Crimper |
Crimp power supply for equipment |
Multimeter |
Check the wiring to ensure it’s correctly connected and without short circuit. |
Clamp Meter |
Test operating current of the air conditioner |
Check Items |
Step Description |
Maintenance Cycle |
Casing |
Use brush or vacuum cleaner to clean the odds and ends on the casing. |
6 months |
Wiring |
Check if it gets loose and if the power supply voltage is normal. |
6 months |
Fans Abnormal |
Move the fans to check if the rotation is smooth, and if there’s abnormal noise or odds and ends. |
6 months |
Cooling Fin |
Use brush or vacuum cleaner to clean the dust on the cooling fin; use water or compressed air to clean the condenser. |
6 months |
Water Drainage |
Check if the water drainage pipe is smooth |
1 year |
Cooling/Heating |
At normal operating status, the measured temperature difference between inside and outside temperatures is higher than 10°C. |
1 year |
Cable |
Check if cable peeling occurs. |
1 year |
Communication Cable |
Check if the cable includes hidden danger such as peeling. |
1 year |
Grounding Cable |
Test if the equipment grounding and cabinet grounding is normally connected, and the resistance is lower than 0.1Ω. |
1 year |
Failures
Failure |
Analysis |
Air conditioner doesn’t work |
Without power input or internal power line may peel. |
Temperature failure alarm |
The temperature probe terminal may be loose, or the probe doesn’t work. |
Fans don’t rotate. |
Check if the power supply is normal, if the cables peels or fan blades are blocked by odds and ends. |
Fans have abnormal noise. |
fan blades are interfered by odds and ends, or fans are damaged. |
Can’t drain condensated water. |
The water drainage pipe is blocked. |