Product Details:
Payment & Shipping Terms:
|
Item |
Type |
Technical Parameter |
Structure |
Dimension |
H*W*D 2000*1600*800mm |
Layout |
Two compartments (left compartment and right compartment, with midlle division plate). |
|
Equipment Installation Method |
19” rack |
|
Door |
With two front doors, and special lock for outdoor cabinet (support padlock) |
|
Material |
Galvanized steel; double wall |
|
Heat Insulation |
There are heat insulation between inner wall and outer wall. The insulation material is 20mm PEF. |
|
Structure |
Assembled |
|
Ingress Protection |
IP55 |
|
Temperature Control |
Cooling |
(AC220V air conditioner+ 48V to 220V inverter) and DC48V fans for left compartment and right compartment. |
Lighting |
LED lamp |
48V LED lamps; The lamps will be on when the cabinet door is open, and will be off when the cabinet door is closed. |
Temperature |
Temperature |
Working Temperature: -40°C ~ +55°C |
Storage Temperature: -50°C ~ + 70°C |
||
Transport Temperature: -50°C ~ +70°C |
||
Humidity |
Relative Humidity |
5% ~ 100% |
Pressure |
Air Pressure |
62kpa ~ 101kpa (similar to 0m ~ 5000m altitude) |
Radiation Intensity |
Solar Radiation Intensity |
1120 ×(1±5%)W/m2 |
No. |
Item |
Quantity |
Unit |
Specs |
1 |
Two Compartment Outdoor Telecom Cabinet |
1 |
Set |
External Dimension: H*W*D 2000*1600*800mm |
2 |
Air Conditioner |
2 |
Set |
Cooling Capacity: 1KW, AC220V; Model:TC06-100SEH/01 |
3 |
Embedded Telecom Power System |
1 |
Set |
2U, 19", 48V, 90A; |
4 |
Inverter |
2 |
Set |
48V to 220V (for air conditioner power supply) |
5 |
Fan |
4 |
Set |
12038, DC48V, START WORK AT 35℃ |
6 |
Power Distribution |
1 |
Set |
GRADE B LIGHTNING PROOF AC INPUT: 63A/2P *1; AC OUTPUT: 16A/1P*4; DC OUTPUT: 16A/1P*4 |
7 |
Lead Acid Battery |
8 |
Set |
12V, 100AH; Model: SP12-100 |
8 |
Temperature and Humidity Sensor |
2 |
PC |
|
9 |
Environment Monitoring Unit |
1 |
Set |
2U |
10 |
Door Sensor |
4 |
PC |
|
11 |
Water Sensor |
2 |
PC |
|
12 |
Smoke Sensor |
2 |
PC |
|
13 |
LED Lamp |
2 |
PC |
|
14 |
Package |
1 |
Set |
Wooden Case |
Cooling Diagram:
Compressor Air Conditioner Cooling Diagram (The red is hot air , and the green is cold air)
Fan Cooling Diagram (The red is hot air , and the green is cold air)
Cabinet Dimension Diagram