Power System of High Performance and High Reliability
GPE48200N Embedded Power System
Configuration |
Rectifier Module |
Monitoring Module |
Power Distribution |
Remark |
Standard Configuration |
GPR4850D-R01 |
GPM48P-A (with Ethernet interface) |
AC power distribution: single-phase input, AC mains MCB (63A/2P); (three phase input optional, modification would reduce 4 output MCBs) DC power distribution: Battery MCB 100A *2; LVD1: 100A*1, 32A*2, 63 A*2, 16 A*4 (MCB capacity optional) LVD2: 16 A*2, 32 A*2 (MCB capacity optional) |
For more tech info, please read specifications. |
1.2 Performance Index
Environment |
|||||||||||
Item |
Min. |
Typical |
Max. |
Unit |
Remark |
||||||
Operating Temperature |
-25 |
|
55 |
° C |
≥ 55°C, the power need to lower the power output. |
||||||
Storage Temperature |
-40 |
|
80 |
° C |
|
||||||
Humidity |
10 |
|
90 |
% |
Relative humidity, non-condensing. |
||||||
Atmospheric Pressure |
70 |
|
106 |
KPa |
|
||||||
Altitude |
0 |
|
3000 |
m |
|
||||||
Cooling |
Forced cooling fan |
||||||||||
Input |
|||||||||||
Item |
Min. |
Typical |
Max. |
Unit |
Remark |
||||||
Input Voltage Range |
90 |
220 |
290 |
Vac |
|
||||||
Input Frequency |
45 |
50 |
65 |
Hz |
|
||||||
Max. Input Current |
|
|
67 |
A |
|
||||||
Power Factor |
0.98 |
|
|
|
Rated load |
||||||
Input Over-Voltage Protection Point |
300 |
|
|
Vac |
Automatic recovery |
||||||
Input Over-voltage Recovery Point |
290 |
|
|
Vac |
Backlash is not less than 5V |
||||||
Input Undervoltage Protection Point |
|
|
85 |
Vac |
Automatic recovery |
||||||
Input Undervoltage Recovery Point |
|
|
90 |
Vac |
Backlash is not less than 5V |
||||||
Input Overcurrent Protection |
|
|
|
|
AC input has air switch for protection. |
||||||
Output |
|||||||||||
Item |
Min. |
Typical |
Max. |
Unit |
Remark |
||||||
Output Voltage |
42 |
53.5 |
58 |
Vdc |
Adjustable by monitoring, no-load test |
||||||
Output Power |
|
10700 |
|
W |
176 ~ 290VAC input, 10700W output (rated power, including battery charging power and load power.) |
||||||
|
5350 |
|
W |
90 ~ 175VAC input |
Table (1) Room Environment Conditions
Environment Conditions |
Recommended Range |
Ambient Temperature |
- 25 ~ + 55 ° C |
Humidity |
≤ 95% RH, non-condensing |
Dust Degree |
≤ 1mg/m3 |
Sunlight |
No direct exposure |
Corrosive Substance |
Free of contaminants, such as salts, acids, and smoke. |
Shock |
≤ 1.5m / s2 |
Insects, pests, animal pests, termites |
No |
Mildew |
No |
Damp |
Rainproof |
Fireproof |
No flammable material on cabinet top and bottom. |
8.2.3 Connect RS232/RS485 Converter
8.2.4 Login
Step Four: Fill in the name, and click “OK” as shown below.
Step Five: Select the following figure.
Step Six: Right-click, select “Comm. Para Settings”.
Step Seven: Select the port number and RS485 Port, click "OK”.
Step Eight: Double-click the following diagram.
8.2.5 LAN Communication Mode Connection