Product Details:
Payment & Shipping Terms:
|
Power System of High Performance and High Reliability
GPE48200N Embedded Power System
|
Configuration |
Rectifier Module |
Monitoring Module |
Power Distribution |
Remark |
|
Standard Configuration |
GPR4850D-R01 |
GPM48P-A (with Ethernet interface) |
AC power distribution: single-phase input, AC mains MCB (63A/2P); (three phase input optional, modification would reduce 4 output MCBs) DC power distribution: Battery MCB 100A *2; LVD1: 100A*1, 32A*2, 63 A*2, 16 A*4 (MCB capacity optional) LVD2: 16 A*2, 32 A*2 (MCB capacity optional) |
For more tech info, please read specifications. |
1.2 Performance Index
|
Environment |
|||||||||||
|
Item |
Min. |
Typical |
Max. |
Unit |
Remark |
||||||
|
Operating Temperature |
-25 |
|
55 |
° C |
≥ 55°C, the power need to lower the power output. |
||||||
|
Storage Temperature |
-40 |
|
80 |
° C |
|
||||||
|
Humidity |
10 |
|
90 |
% |
Relative humidity, non-condensing. |
||||||
|
Atmospheric Pressure |
70 |
|
106 |
KPa |
|
||||||
|
Altitude |
0 |
|
3000 |
m |
|
||||||
|
Cooling |
Forced cooling fan |
||||||||||
|
Input |
|||||||||||
|
Item |
Min. |
Typical |
Max. |
Unit |
Remark |
||||||
|
Input Voltage Range |
90 |
220 |
290 |
Vac |
|
||||||
|
Input Frequency |
45 |
50 |
65 |
Hz |
|
||||||
|
Max. Input Current |
|
|
67 |
A |
|
||||||
|
Power Factor |
0.98 |
|
|
|
Rated load |
||||||
|
Input Over-Voltage Protection Point |
300 |
|
|
Vac |
Automatic recovery |
||||||
|
Input Over-voltage Recovery Point |
290 |
|
|
Vac |
Backlash is not less than 5V |
||||||
|
Input Undervoltage Protection Point |
|
|
85 |
Vac |
Automatic recovery |
||||||
|
Input Undervoltage Recovery Point |
|
|
90 |
Vac |
Backlash is not less than 5V |
||||||
|
Input Overcurrent Protection |
|
|
|
|
AC input has air switch for protection. |
||||||
|
Output |
|||||||||||
|
Item |
Min. |
Typical |
Max. |
Unit |
Remark |
||||||
|
Output Voltage |
42 |
53.5 |
58 |
Vdc |
Adjustable by monitoring, no-load test |
||||||
|
Output Power |
|
10700 |
|
W |
176 ~ 290VAC input, 10700W output (rated power, including battery charging power and load power.) |
||||||
|
|
5350 |
|
W |
90 ~ 175VAC input |
|||||||
Table (1) Room Environment Conditions
|
Environment Conditions |
Recommended Range |
|
Ambient Temperature |
- 25 ~ + 55 ° C |
|
Humidity |
≤ 95% RH, non-condensing |
|
Dust Degree |
≤ 1mg/m3 |
|
Sunlight |
No direct exposure |
|
Corrosive Substance |
Free of contaminants, such as salts, acids, and smoke. |
|
Shock |
≤ 1.5m / s2 |
|
Insects, pests, animal pests, termites |
No |
|
Mildew |
No |
|
Damp |
Rainproof |
|
Fireproof |
No flammable material on cabinet top and bottom. |
![]()
8.2.3 Connect RS232/RS485 Converter
![]()
8.2.4 Login
Step Four: Fill in the name, and click “OK” as shown below.
![]()
Step Five: Select the following figure.
![]()
Step Six: Right-click, select “Comm. Para Settings”.
![]()
Step Seven: Select the port number and RS485 Port, click "OK”.
![]()
Step Eight: Double-click the following diagram.
![]()
![]()
8.2.5 LAN Communication Mode Connection