Product Details:
Payment & Shipping Terms:
|
Power System of High Performance and High Reliability
STC-CPL48120ER Embedded Power System
Input: 90~280Vac; Output:-43.2~-57.6Vdc; Power: 6420W
Features
(1) Total capacity: -53.5Vdc/(10~120)A
(2) Standard 19in./3U,easy to be embedded to all kinds of telecom equipment and cabinets
(3) Adoption of active power factor compensation
(4) Normal operating range of AC input voltage: 90~280Vac
(5) Operating temperature range: -20℃~ +65℃
(6) Adoption of softswitch tech with efficiency of 91% or above
(7) Perfect battery management, LVLD&BLVD
(8) Hot pluggable
(9) Excellent lightning proof design applicable to areas with frequent thunderstorms
(10) Input over/under voltage protection
(11) Output over voltage/current protection
(12) Output short circuit protection
(13) LED indicators on front panel
(14) Compliant to UL 60950, CSAC22.2 60950-00, VDE0805 IEC60950
(15) CE mark meets directives of 73/23/EEC and 93/68/EEC
Application
(1) Program controlled exchanger
(2) Access network
(3) Transmission equipment
(4) Mobile communication
(5) Satellite communication ground station
(6) Microwave communication
Basing on years development and operating experience, the embedded power system is a newly-designed product, which is of high performance and high reliability. The system size is standard 19in. /3U, can be embedded into all kinds of telecom equipments and cabinets. It is also of wide range of input voltage and operating temperature, high efficiency and the hot plug makes it is easy for maintenance.
1. System operating principle
AC power is first input AC-INPUT circuit breaker and then fed into the rectifier module after the EMI filtering. AC-INPUT functions as over load and short circuit protection to AC power. Load LVD contactors KM1, KM2 are connected in series with the LOAD1 and LOAD2. The user’s battery is connected to the DC output through BAT circuit breaker and KM2, and the circuit breaker provides disconnection control, over-load and short-circuit protection to the battery.
Under normal conditions, every parameter of rectifier modules and distribution unit are all under control of the monitoring module, operating according to the pre-set parameter or user’s commands. If AC mains fault, the battery will power to the system. With the battery discharge, the terminal voltage of the battery starts to descend. When the battery voltage drops to below -47V (settable), the monitoring module will report the DC under-voltage alarm signal. When the voltage drops to -45.0V (settable), the monitoring module will make KM1 cut off LOAD1 while retaining LOAD2.The power system just powers to LOAD2. When the voltage drops below -43.0V (settable), the KM2 acts to cut off LOAD2 output, then the power system stops working. When the external AC mains recovers, the system will resume to the normal work state. (All above monitoring data are system default values, users can reset).
Except for battery over-discharge protection, battery or load over-temperature protection function is prohibitive under default condition, users can send command to activate or inactivate according to the demand.
2. System configuration
2.1 4 Nos rectifier modules
Options: CPL4810RM, CPL4815RM, CPL4820RM, CPL4830RM;
2.2 1 Nos monitoring module
Options: CPL48D(RS485, LCD), CPL48DI (RS485, TCP/IP, LCD), CPL48I(RS485);
2.3 1 Nos surge protection module (20KA)
2.4 Distribution part .
AC Distribution: single phase, 3 lines, double-pole AC breaker 60A of general power supply;
DC Distribution: battery fuse 80A×1;
LVBD: 100A×1;
LVLD: 200A×1
1. AC input socket-3 core 2. Fixing hole
3. MCB 4. Surge protection module
5. Rectifier module 6. Monitoring module
7. Load output connectors
3. Line diagram:
4. Properties
(The specifications are for system configured with 2 Nos rectifiers of 30A if not specified.)
Input |
||||||
Parameter |
Min. |
Typical |
Max. |
Unit |
Remark |
|
Input voltage range |
90 |
220 |
280 |
Vac |
|
|
Input frequency |
45 |
50 |
65 |
Hz |
|
|
Input current |
|
|
37.3 |
A |
|
|
Power factor |
0.98 |
|
|
|
|
Output |
||||||
Parameter |
Min. |
Typical |
Max. |
Unit |
Remark |
|
Output voltage range |
-43.2 |
-53.5 |
-57.6 |
Vdc |
|
|
Output current range |
4Nos rectifiers of 30A |
0 |
|
120 |
A |
175~280VAC |
0 |
|
60 |
A |
150~175VAC |
||
0 |
|
45 |
A |
90~150VAC |
||
4Nos rectifiers of 20A |
0 |
|
80 |
A |
175~280VAC |
|
0 |
|
45 |
A |
90~175VAC |
||
4Nos rectifiers of 15A |
0 |
|
60 |
A |
175~280VAC |
|
0 |
|
37.5 |
A |
90~175VAC |
||
4Nos rectifiers of 10A |
0 |
|
40 |
A |
175~280VAC |
|
0 |
|
20 |
A |
90~175VAC |
||
Regulation |
|
|
±1 |
% |
|
|
Load regulation |
|
|
±1 |
% |
|
|
Line regulation |
|
|
±1 |
% |
|
|
Weighted psophometric noise |
|
|
2 |
mv |
|
|
Wide frequency noise voltage |
|
|
50 20 |
mv mv |
3.4KHz~150KHz 150KHz~30MHz |
|
Ripple(Vp-p) |
|
|
200 |
mv |
Rated input/ output, add 0.1uFfilm capacitor and 10uF high frequency electrolyte capacitor, oscilloscope band width is20MHz |
|
Current sharing |
|
|
±5 |
% |
|
|
Output power |
|
|
6420 |
W |
4Nos rectifiers of 30A |
|
|
|
4280 |
W |
4Nos rectifiers of 20A |
||
|
|
3210 |
W |
4Nos rectifiers of 15A |
||
|
|
2140 |
W |
4Nos rectifiers of 10A |
||
Output efficiency |
91 |
|
|
% |
220Vac input |
|
83 |
|
|
% |
110Vac input |
Protection |
|
||||||
|
Parameter |
Unit |
Min. |
Typical |
Max. |
Recovery Property |
|
|
Input over-voltage |
Vdc |
285 |
305 |
|
Auto recovery |
|
|
Input over-voltage recovery set point |
Vdc |
280 |
|
|
Hysteresis not less than 5V |
|
|
Input under-voltage |
Vdc |
|
|
85 |
Auto recovery |
|
|
Input under-voltage recovery set point |
Vdc |
|
|
90 |
Hysteresis not less than 5V |
|
|
Output over-voltage protection set point |
V |
58.5 |
59 |
61.5 |
Lock up |
|
|
Output current limiting |
A |
96 |
99 |
102 |
Auto recovery |
|
|
Short circuit |
A |
Long-term short circuit permissible; Hiccup when short circuit detected |
||||
|
Thermal protection |
℃ |
Auto recoverable under ambient temperature of 60℃. |
||||
|
Fan failure |
|
When one fan fails, the module runs with automatic derating and reports alarm till the module high temp protection cuts off the output. When both fans fail, the module cuts off output after reporting alarm. |
Ambient |
|||||
Parameters |
Min |
Typical |
Max |
Unit |
Remark |
Operating temp. |
-25 |
|
55 |
°C |
|
Extended operating temp. |
55 |
|
75 |
°C |
Operation with derating |
Storage temp. |
-45 |
|
85 |
°C |
|
Humidity |
5 |
|
95 |
% |
Relative humidity, non-condensing |
Altitude |
-60 -200 |
|
4000 13000 |
m ft |
For operation above 2500m (5000 ft.), the maximum operation temperature is derated by 2°C. per 305m (1000 ft.) |
Shock and vibration operation test standard drop and tumble |
|
|
|
|
IEC 68-2 IEC 721-3-2 IEC 68-2-31 |
Earthquake rating |
4 |
|
|
Zone |
|
Noise |
|
45 |
|
dB |
Relative to fan speed, load and ambient temperature |
Harmonic emission |
EN/IEC61000-3-2 |
||||
Radiated emission |
EN55022 - Class B |
||||
Conducted emission |
EN55022 - Class B |
||||
ESD |
EN/IEC 61000-4-2 Level 3 (Contact Discharge 6 kV, Air Discharge 8 kV). |
||||
Radiated immunity |
EN/IEC 61000-4-3 Level 3 (10 V/m). |
||||
Conducted immunity |
EN/IEC 61000-4-6 Level 3 (10Vrms). |
||||
EFT/B |
EN/IEC 61000-4-4 Level 3 (2 kV, 5 kHz Repeat) |
||||
Lightning surge |
Common mode 4kV, differential mode 2kV. AC input should bear lightning strike impact current waveform of 8/20us, ±5 times for impacts of 5KA |
||||
Isolation properties input-chassis input - output output - chassis |
1500 3000 500 |
|
|
Vac Vac Vdc |
|
Leakage current |
|
|
3.5mA |
|
264Vac Input |
Insulation resistance |
10MΩ |
|
|
|
Tested at 500Vdc |
Mechanical spec. |
|
Length (in./mm) |
19/482.6 |
Width (in./mm) |
10/255 |
Height (in./mm) |
5.14/130.5 |
Weight (kg) |
≤11 |
5. Dimensional diagram