Product Details:
Payment & Shipping Terms:
|
STC-CPL48150ER Embedded Power System
Input:90~290Vac; Output: -42~-58Vdc;
Main features
1. Adoption of active power factor compensation technology with factor >0.98
2. Wide operating range of AC input voltage: 90~290Vac
3. Operating temperature range: -25℃~+55℃
4. Zero current/voltage switching tech with high efficiency ≥91%
5. Lifecycle of battery prolonged by perfect battery management, including electrical charge/discharge management, battery temperature compensation, battery capacity test, reversal connection proof protection
6. Hot-swappable
7. Input over/under voltage protection
8. Output over voltage protection
9. Output over current protection
10. Output short circuit protection
11. Auto current sharing
12. Embedded mounting
Application
■ Small scale program controlled exchanges
■ Access network
■ Transmission equipment
■ Mobile communication
■ Satellite communication ground station
■ Microwave communication
The STC-CPL48150ER embedded power system consists of the distribution frame, monitoring module and rectifier module, with functions of AC lightning proof and DC current sharing. The monitor module supports outside signal input, communication transformation, AC/DC detection and contactor control. The whole system is of high reliability and performance, and can be operated through PC software.
1. General Introduction 1.1 System configuration
The system consists of distribution unit, rectifier module (from 1 set, up to 3 sets) and monitoring module. The configuration is optional, as following table:
Configuration |
Rectifier Module |
Monitoring Module |
Distribution |
Remark |
Standard |
STC-CPL4850RM |
STC-CPL-MA (With Ethernet Port) |
AC distribution: 3-phase, 4-wire input, 4-pole AC breaker @ general line (32A); DC distribution: Battery fuse 100A×2; LVLD: 32A×4 16A×2 10A×2 LVBD: 63A×2 |
For details, please refer to the specifications of modules. |
1.2 Operating principle
AC power is first input AC-INPUT MCB and then fed into the rectifier module after the EMI filtering. AC-INPUT acts as protection to over load and short circuit to AC power. The user’s battery is connected to the DC output side through MCB BAT and KM2, and the circuit breaker provides disconnection control, over-load and short-circuit protection to the battery.
Under normal conditions, every parameter of rectifier modules and distribution unit are all under control of the monitoring module, operating according to the pre-set parameter or user’s commands. If AC mains faults, the battery will power to the system. With the battery discharge, the terminal voltage of the battery starts to descend. When the voltage is under -47V±0.5V, the monitor send DC under voltage alarm signal and when the voltage is under -46.0V±0.5V (adjustable), the KM1cuts off non-priority loads and retaining power to priority loads. If the voltage drops to -43.0V±0.5V (adjustable), the KM2 will cut off output of priority loads and then the power system will stop working. If the external AC mains recovers, the system will normally work again. (All above monitoring data are system default values and can be reset by user).
Except for battery over-discharge protection, battery or load over-temperature protection is prohibitive under default, users can send command to activate or inactivate according to the demanding.
2. System Properties
2. 1 System Properties
Environment |
|||||
Item |
Min. |
Typical |
Max. |
Unit |
Remark |
Operating temperature |
-25 |
|
55 |
°C |
When ≥55°C, decreased power output |
Storage temperature |
-40 |
|
80 |
°C |
|
Humidity |
10 |
|
90 |
% |
Relative humidity without condensing |
Atmospheric pressure |
70 |
|
106 |
KPa |
|
Altitude |
0 |
|
3000 |
m |
|
Cooling |
Forced cooling with fan |
Input |
|||||
Item |
Min. |
Typical |
Max. |
Unit |
Remark |
Input voltage range |
90 |
220 |
290 |
Vac |
|
Input frequency |
45 |
50 |
65 |
Hz |
|
Input current |
|
|
20 |
A |
|
Power factor |
0.98 |
|
|
|
Rated load |
Input over voltage protection |
300 |
|
|
Vac |
Automatically recoverable |
Input over voltage recovery |
290 |
|
|
Vac |
Return difference ≥5V |
Input under voltage protection |
|
|
85 |
Vac |
Automatically recoverable |
Input under voltage recovery |
|
|
90 |
Vac |
Return difference ≥5V |
Input over current protection |
|
|
|
|
MCB in AC Input supplied protection |
Output |
|||||
Item |
Min. |
Typical |
Max. |
Unit |
Remark |
Output voltage range |
42 |
53.5 |
58 |
Vdc |
Adjustable by monitor, tested in no load |
Output power |
|
8000 |
|
W |
Make sure rated 4800W output when input voltage is 176~290VAC (rated power includes battery power plus load power) |
|
4000 |
|
W |
150~175VAC input |
|
|
2000 |
|
W |
90~150VAC input |
|
Output over voltage protection |
58.5 |
|
60.5 |
Vdc |
Lock up |
Output current limiting protection |
|
|
|
|
Current limiting protection |
Output short circuit protection |
|
|
|
|
Long-term short circuit protection, automatically recoverable |
Over temperature protection |
|
|
|
|
Automatically recoverable in normal temperature 65℃ |
Battery power-down protection |
|
|
|
|
Battery power-down protection |
Battery polarities reversal connection protection |
|
|
|
|
No damage on battery and power system |
Voltage withstand efficiency |
|
|
±1 |
% |
|
Normal Parameters |
|||||
Item |
Min. |
Typical |
Max. |
Unit |
Remark |
Temperature coefficient |
|
|
±0.2 |
‰/℃ |
|
Current sharing unbalance |
|
|
±5 |
% |
Within 50~100%load range |
Start-up/shunt-down overshoot range |
|
|
±5 |
% |
Any module is removed when operating, (the load current should be less than total output current), the system output voltage fluctuates |
Dynamic response recovery time |
|
|
200 |
uS |
25%~50%~25% load variation 50%~75%~50% load variation |
Dynamic response overshoot |
|
|
±5 |
% |
Rated output voltage, rated load current |
Efficiency |
90 |
92 |
|
% |
220Vac input, rated input voltage, rated load current |
83 |
|
|
% |
110Vac input, rated output voltage, rated load current |
|
Start-up time |
3 |
|
8 |
S |
pre-current limiting is fitted with start-up output between rated start up input voltage and rated output voltage established period |
Pressure drop |
|
|
500 |
mV |
|
Peak-peak noise voltage |
|
|
200 |
mV |
|
Psophometrically weighted noise voltage |
|
|
2 |
mV |
|
Other Parameters |
|
Item |
Requirement |
Acoustic noise |
≤55dB(A) |
Smelling |
any abnormal and poisonous smelling is not allowed |
Components |
rated temperature of the electrolytic capacitor ≥105℃ |
Hot swappable |
the rectifier module meets the hot-swappable requirement |
Mixed insertion |
rectifier modules can mixed insertion |
Ineffective separation |
rectifier module can separate with system when it is ineffective |
Cooling |
Forced cooling by fan mounted on rectifier, face in, back out. The fan is mounted on rectifier front panel; can be disassembled. Fan speed and temperature can be controlled by user |
Insulation Rating |
|||||
Parameters |
Min. |
Typical |
Max. |
Unit |
Remark |
Input-chassis |
|
750 |
|
Vdc |
|
Input-output |
|
1414 |
|
Vdc |
|
Output-chassis |
|
750 |
|
Vdc |
|
Insulating Resistance |
relative humidity is 90%, |
3. STC-CPL48150ER Distribution Frame