Product Details:
Payment & Shipping Terms:
|
Configuration |
Rectifier module |
Monitoring module |
Distribution |
Remark |
Standard |
GPR4830A1 |
|
DC Output:30A×1route(load) Battery Output:30A×1route(battery) |
For details, please refer to the specifications of modules |
Standard |
GPDA1000VA-G |
220VACOutput:5A×1route (load) |
1.3 GPEM1500-A Specification
Input |
||||||
Parameter |
Min. |
Typ. |
Max. |
Unit |
Remark |
|
Rectifier module |
Input voltage range |
90 |
220 |
280 |
Vac |
Nominal operating voltage range: 100V-240V |
Input frequency |
45 |
50 |
65 |
Hz |
|
|
Startup inrush current |
|
|
50 |
A |
25°C cold start,280Vac input,full-load |
|
Power factor |
0.99 |
|
|
|
220Vac input,output full-load |
|
Conversion module |
Input voltage range |
43 |
|
58 |
Vdc |
|
Startup inrush current |
|
|
45 |
A |
25°C cold start,< 150% of rated current |
Output |
|||||
Parameter |
Min. |
Typ. |
Max. |
Unit |
Remark |
Rectifier module voltage adjustable range |
-43.2 |
-54 |
-57.6 |
Vdc |
Default output 54V(adjustable by monitor) |
Conversion module output voltage range |
|
220 |
350 |
Vac |
Default output220Vac |
Rectifier module current range |
0 |
|
30 |
A |
176~280Vac input |
Conversion module current range |
0 |
|
4.28 |
A |
43~58Vdc input |
Ripple (Vp-p) |
|
|
200 |
mV |
Rated input and load, Apply a 0.1uF ceramic capacitor and 10uF electrolyte capacitor to output, oscilloscope bandwidth of 20MHz. |
Stabilized voltage precision |
|
|
±2 |
% |
|
Load regulation |
|
|
±2 |
% |
|
Voltage regulation |
|
|
±1 |
% |
|
Rectifier module output power |
|
|
1600 |
W |
176-280Vac input |
|
|
800 |
W |
90-175Vac input |
|
Conversion module output power |
|
|
800 |
W |
Conversion module output power |
Bypass conversion duration |
Duration for conversion to AC output≤20ms; Duration for AC to conversion output≤10ms
|
||||
AC bypass function |
Bypass outputs when AC is normal, Conversion outputs when AC is abnormal. |
Insulation rating |
||
parameter |
Standard |
Remark |
Insulating strength(AC input) |
Input-Output:3500Vdc/10mA//1min |
No flashover or breakdown. Remove discharge tube/surge protection device before testing, no rectifier module or monitoring module. Output with 2 routes low-voltage terminal, high-voltage with AC bypass function, not to be tested. |
Input-enclosure:3500Vdc/10mA//1min |
||
Output-enclosure:750Vdc/10mA//1min |
||
Insulating strength(DC input) |
Input-Output:750Vdc/10mA//1min |
|
Input-enclosure:750Vdc/10mA//1min |
||
Output-enclosure:750Vdc/10mA//1min |
||
Leakage current |
≤3.5mA |
280Vac input,output full-load |
Insulation resistance |
@ Normal atmosphere, relative humidity of 90%, Test voltage of DC 500V,the insulation resistance of input-output, input-ground, output-ground shall not be less than 10MΩ. Output with 2 routes low-voltage terminal, high-voltage with AC bypass function, not to be tested. |
Environment |
|||||
Parameter |
Min. |
Typ. |
Max. |
Unit |
Remark |
Operation temperature range |
-5 |
25 |
+55 |
°C |
|
Storage temperature |
-40 |
|
+70 |
°C |
|
Relative humidity |
5 |
|
95 |
% |
Long-term operating, no condensing |
Atmosphere pressure |
70 |
|
106 |
KPa |
|
Altitude |
0 |
|
3000 |
m |
|
Cooling |
Forced cooling, front-in & rear-out; the fan locates in front panel, with temperature controlled speed. |
||||
Water & dust proofing level |
The power supply shall work properly under the following condition: density of dust diameter above 55µm≤3*104 granule/m3. The dust granule is non-conductive, non-electromagnetic, non-corrosive, without water-proof function. |
Mechanical specification |
|
Dimension |
As figure below |
Weight (overall) |
≤6.3Kg(with module) ≤3.3Kg(without module,plug-in frame) |
2. Installation
3. Electrical connection
Data |
Signal |
Remark |
Analog data |
Rectifier module output current,bus bar voltage,battery current,load current,battery temperature |
The monitoring module sends parameters and alarm to the host. |
Digital data & alarms |
module failure, DC under/over voltage, Primary power down, module start-up/shutdown, battery equalizing/float charge, battery over current |
|
Parameters setup |
Equalizing charge voltage, float charge voltage, DC output over- voltage alarm point, battery under-voltage alarm point, battery power down alarm point, battery capacity, Temperature compensation coefficient, Coefficient of equalized charging to floating charging, Coefficient of floating charging to equalized charging |
The host sets the parameters and orders to the monitoring module. |
Controlling orders |
rectifier module start / shutdown, conversion module start / shutdown temperature compensation on/off |
Type |
Description |
Battery rectifying |
The system background outputs alarm when the output voltage is under preset battery rectifying. |
Battery power down |
Under situation of battery discharge, when the voltage is below preset battery shutdown voltage, the battery DC relay will break off and shutdown all loads, cut off the connection between battery and system. The system will not work until the re-power on. |
Battery configure |
1. Fixed current charging: when the configuration is the 20-50Ah battery, the charge coefficient will be set to 5A; when the configuration is the 50-100Ah battery, the charge coefficient will be set to 10A. Specific settings such as the electrical connection diagram shown in the port 5 (temperature compensation port and the battery charging coefficient adjustment port), to adjust the dial code and set to the corresponding 5A/10A. (system default settings) 2. Adjustable current charging: through the background monitoring software to open the adjustable charge current switch and set the value of the charge current. (optional) |
Battery equalizing/float charge management |
When the battery charge current is high than pre-set upper value, the system will conduct equalizing charge of constant current (CC). If the CC equalizing charge reaches equalizing charge voltage, the system will act equalizing charge of constant voltage (CV). The system will float charge when the CV equalizing charge current is below current of equalizing charge shift to float charge. Under situation of float charge current more than current of float charge shift to equalizing charge, and the duration of system equalizing/float charge reaches preset time, the system will automatically equalize charge. The system will automatically shift to float charge if CV equalizing charge duration exceeds preset value and the manual equalized charge will change over to equalizing charge. |
Temperature compensation |
Under situation of temperature compensation on, when the battery temperature is above 25℃, the system acts temperature compensation and if the battery temperature is below 25℃, the system acts minus compensation. The compensation value (equals to temperature*coefficient) shall not be greater than 2V. |
Name |
Type |
Output state |
Contact 1 |
General alarm |
Break off when alarm switch on when normal |
Contact 2 |
rectifier module alarm |
Break off when alarm switch on when normal |
Contact 3 |
conversion module alarm |
Break off when alarm switch on when normal |