Product Details:
Payment & Shipping Terms:
|
|
Model No. |
TC06-20TEH/01 |
|
Cooling Method |
air to air |
|
Cooling Object |
air |
|
Cooling Object Contact Medium |
air |
|
Cooling Effective Power |
200W |
|
Input Voltage |
DC48V (43V~58V) |
|
Cooling Stable Current |
7.0±5%A |
|
Installation Mode |
side |
|
Noise |
58dB |
|
MTBF |
70000h |
|
Size (LxWxH) |
400x180x203mm |
|
Weight |
7.5Kg |
|
Environmental Performance |
working environmental temperature |
-40°C ~ 60°C |
|
|
storage working temperature |
-50°C ~ 70°C |
|
|
working humidity |
≤95% |
|
Thermal Performance |
rated cooling capacity |
200W |
|
|
heating input power |
300W |
|
Electrical Performance |
rated input current |
6.8A |
|
|
rated input power |
330W |
|
|
input voltage |
DC48V |
2.3 Dimension
![]()
Diagram 3: TC06-20TEH/01 dimension
3. Control
![]()
|
Parameter No. |
Parameter Name |
Initial Value |
Remark |
|
P00 |
FSV |
|
current feedback value, unit: A |
|
P01 |
Fr1 |
|
fan rotating speed 1, per second |
|
P02 |
Fr2 |
|
fan rotating speed 2, per second |
|
P03 |
LOC |
0 |
password parameter, LOC=55, accessible to the following parameters; LOC=77, recover parameter setting when devivery. |
|
P04 |
colTa |
28.0 |
cooling start temperature |
|
P05 |
colTb |
2.0 |
cooling control return difference |
|
P06 |
hotTa |
10.0 |
heating start temperature |
|
P07 |
hotTb |
2.0 |
heating control return difference |
|
P08 |
ZFanTa |
35.0 |
straight ventilation start temperature |
|
P09 |
ZFanTb |
2.0 |
straight ventilation control return difference |
|
P10 |
tecAL |
0.5 |
TEC current lower limit |
|
P11 |
tecAH |
20.0 |
TEC current upper limit |
|
P12 |
TAL |
5.0 |
internal temperature alarm lower limit |
|
P13 |
TAH |
45.0 |
internal temperature alarm upper limit |
|
P14 |
BT |
0.0 |
temperature deviation correction |
|
P15 |
fanEN |
0 |
allow fan fault judgement |
|
P16 |
tecEN |
1 |
allow TEC fault judgement |
|
P17 |
ADR |
1 |
communication address |
|
P18 |
BAUD |
2 |
baud rate:0~3, (2400~19200BPS) |
|
P19 |
inOH |
100 |
inside fan speed limit |
|
P20 |
outOH |
100 |
outside fan speed limit |
|
P21 |
fsvX |
1.0 |
current feedback correction coefficient (amplifying coefficient) |
|
P22 |
pqTa |
80 |
hydrogen exhaust cycle (hour); auto hydrogen exhaust every 30 minutes after starting cooling; can press pqTa to define hydrogen exhaust cycle. |
|
P23 |
pqTb |
2 |
hydrogen exhaust time length(minute) |
4. Mainboard Wiring Diagram
![]()